beautypg.com

Ratings, Boiler manual – Weil-McLain ULTRA 80 EN User Manual

Page 44

background image

Part number 550-101-233/0903

GAS

-

FIRED

WATER

BOILER

— Boiler Manual

44

Ratings

DOE

1

. As an Energy Star Partner, Weil-McLain has determined

that Ultra boilers meet the Energy Star guidelines for energy
efficiency.

2. Based on standard test procedures prescribed by the United

States Department of Energy.

3. Net I=B=R ratings are based on net installed radiation of

sufficient quantity for the requirements of the building
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of
1.15. An additional allowance should be made for unusual
piping and pickup loads.

4. Ultra boilers require special venting, consistent with

Category IV boiler. Use only the vent materials and
methods specified in Ultra vent supplements. Ultra boilers
must be direct-vented. Ultra-230 can be vented with either
3" or 4" vent pipe. Vent length limits for 3" vent are not as
long as for 4" vent.

Notes

Notes

5. Weil-McLain Low temperature seasonal efficiency is based

on ASHRAE 103 test method, using boiler return water
temperature of 90°F, with boiler outlet water temperature
of 110°F.

6. Combustion efficiency is based on I=B=R testing procedure

BTS-2000, and equal to 100% minus flue loss.

7. Thermal efficiency is based on I=B=R testing procedure

BTS-2000.

8. Weil-McLain Low temperature efficiency is based on the

I=B=R testing procedures, using boiler return water
temperature of 90°F and boiler outlet water temperature
of 110°F.

9. Ratings shown are for sea level applications only. For

altitudes from sea level to 5,500 feet above sea level, the
Ultra boiler requires no modifications and automatically
derates itself by approximately 4% per 1000 feet above sea
level. For elevations above 5,500 feet, contact your local
Weil-McLain sales office for details.

11

This manual is related to the following products: