Pro Hood Liner Specifications
7
wolfappliance.com/specs
Installation Specifications
The illustration and chart below provides dimensions
critical for proper installation of the pro ventilation hood
liner. Dimension A in the illustration will vary with the width
of the hood liner. Refer to the chart below.
Pro Hood Liners
WIDTH OF LINER
A
34
3
/
8
"
(873)
17
3
/
16
"
(437)
40
3
/
8
"
(1026)
20
3
/
16
"
(513)
46
3
/
8
"
(1178)
23
3
/
16
"
(589)
52
3
/
8
"
(1330)
26
3
/
16
"
(665)
58
3
/
8
"
(1483)
29
3
/
16
"
(741)
Pro hood liners.
Electrical Requirements
Wolf pro ventilation hood liners require a separate,
grounded 120 V AC, 60 Hz power supply. The service
should have its own 15 amp circuit breaker. Locate the
electrical supply within the shaded area shown in the
installation illustration on the previous page.
IMPORTANT NOTE:
You must follow all National Electrical
Code regulations. In addition, be aware of local codes and
ordinances when installing your service.
A
TO CENTER
OF TRANSITION
9
3
/
8
"
(238)
6"
(152)
Risk of electrical shock. This ventilation hood must be
properly grounded. Electrical service for the hood must
be installed by a qualified electrician in accordance
with all applicable national and local electrical codes.