beautypg.com

Step 10 – Westinghouse Teco MA7200 Plus User Manual

Page 13

background image

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________

________________________________________________________________

TECO – Westinghouse Motor Company

13

Step 10

– Setting PID Parameters; Proportional Gain (Bn-17) and

Integral Time (Bn-18)

• After all external connections have been made and the protective covers have been

replaced, power up the inverter but do not run at this point.

• Parameters

Bn-17 = 1.0 (Proportional Gain) and Bn-18 = 10.0s (Integral Time) are factory

set to the values shown. However, a good starting point for these values is setting the
Proportional Gain Bn-17 = 2.0 and the Integral Time Bn-18 = 5.0s. To change these
parameters, follow the keypad navigation procedure below.

PRGM

DRIVE

DSPL

Bn-01

key

Acc. Time 1

1 - Press the

2 - Press the

4 - Press the

key

key

An – 01 -

Freq. Cmd. 1

EDIT

ENTER

key to save.

6 - Press the

Entry Accepted

2 Seconds

Flashing

EDIT

ENTER

Flashing

To set parameter Bn-17 = 02.0

(Proportional Gain )

Keypad Steps

Resulting Display

3 - Press the

key until the display shows

Bn-17

PID P_ Gain

RESET

key twice; then the

key

5 - Press the

Flashing

Cn-19 = 050%

Freq Cmd Low Bound

Bn-17 = 01.00

PID P_ Gain

Bn-17 = 02.00

PID P_ Gain

Next set Bn-18 = 005.00