Step 9 – Westinghouse Teco MA7200 Plus User Manual

Page 10

background image

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________

________________________________________________________________

TECO – Westinghouse Motor Company

10

PRGM

DRIVE

DSPL

EDIT

ENTER

Sn – 01 -

key twice

Inverter Capacity

Flashing

To set the parameter Sn-24 = 0

Keypad Steps

Resulting Display

1 - Press the

2 - Press the

3 - Press the

key until display shows

4 - Press the

key

(VIN, 0 – 10 VDC)

key

An – 01 -

Freq. Cmd. 1

Sn – 24

Sn – 24 = 1

CMD. AIN

EDIT

ENTER

key to save.

5 - Press the

key

6 - Press the

Entry Accepted

2 Seconds

PRGM

DRIVE

7 - Press the

key to return to the main display.

Flashing

Sn – 24 = 0

CMD. VIN

Flashing

Sn – 24 = 0

External Input

CMD. VIN

Step 9

– Select Feedback Engineering Units (P1-01) and Scaling (P1-02)

Initially the display will read output frequency in (Hz) as the factory default and is set by
parameter (Cn-28=0). If (Cn-28) is changed to (=1), then the display will read out in (%). The
setting of (Cn-28) is only valid if (P1-01=0), which is the factory default. Other engineering units
may be selected by parameter setting (P1-01) as described on the following page.

In this step, the feedback engineering units that the system is controlling such as CPM in fan
applications or PSI in the case of pumps can be selected by parameter (P1-01). (See Appendix
A
for additional selections)
. The maximum value that the engineering units will be in any given
application is set by parameter (P1-02). These selections will now be displayed on the digital
operator.

Example: A pump application that has a feeedback transducer with a maximum value of
200 PSI i.e 200 PSI = 20mA or 10 Vdc, can be set as shown next.