beautypg.com

Pfg s – Weil-McLain SERIES 7 PFG User Manual

Page 14

background image

1

PFG S

erieS

7 G

aS

-

Fired

W

ater

B

oiler

– U

niverSal

C

ontrol

S

yStemS

Part Number 550-110-643/0605

TABLE III: Pilot Lights, Main Valve Will Not Come On

With or Without Vent Damper

Correct wiring.

Make sure sense wire is not wrapped
around any pipe or accessories.

Is sense wire securely attached to sense
terminal and pilot assembly?

No

Yes

Correct.

Replace pilot
assembly.

Replace
valve.

Check for continuity of sense wire
and condition of insulation.

Not OK

OK

Check for proper gas pressure, clean pilot assembly
tight mechanical and electrical connections.
Also check for proper system grounding.
See additional information on page 15.

Does spark stay on for more than a few seconds after pilot is established?

No

Yes

Is sensing probe ceramic
cracked?

No

Yes

Replace pilot
assembly.

Is sense wire or sensing
probe shorted out to
metal surface?

No

Yes

Correct.

Replace ignition control.

Replace ignition
control.

Is 24VAC between Terminals
MV and MV/PV on ignition control?

No

Yes

Contact gas supplier to
correct.

Is inlet gas pressure at least
5.0"W.C. and not over
14"W.C.?

No

Yes

Is main valve wiring secure
at terminals?

No

Yes

No

Yes

Does system have proper flame signal?

Set up microammeter to measure
output current in flame sensor circuit
as follows:

a. Detach sense lead from ignition

control. Attach negative lead
from microammeter to sense
terminal on ignition control.

b. Attach positive lead to sense wire

from pilot assembly.

c. Disconnect main valve lead from

Terminal "MV" on ignition control.

d. Energize the system. Spark should

ignite the pilot. As soon as pilot is
burning, microammeter should
read at least 1.0 microamp for
Honeywell S8620C, 0.1 microamp
for U.T. 1003-510.

e. Is flame current signal less than the

minimum specified in "d" above?