Installation, Horizontal installations – Waterford Appliances T25-LP User Manual
Page 12
12
Waterford TARA T25 Direct Vent Freestanding Gas Stove
Diagram 4
Diagram 2a
Diagram 3
HORIZONTAL
INSTALLATIONS
1) Set the unit in its desired location. Check to
determine if wall studs are in the way when
the venting system is attached. If this is the
case, you may want to adjust the location
of the unit.
2) Assemble the desired combination of pipe
and elbow to the appliance adapter with
pipe seams oriented down. Offset the pipe
seams as double seams in one place will
cause the outer pipe to take an oval shape.
Kit comes complete with 18" of straight vent
- 6-5/8" dia. black outer pipe and 4" dia. inner
vent.
3) With the pipe attached to the stove, slide the
stove into its correct location, and mark the
wall for a 9-1/2" (inside dimensions) round
hole. The center of the round hole should
line up with the centerline of the horizontal
pipe, as shown in diagram 1. Cut and frame
the 9-1/2 round hole in the exterior wall
where the vent will be terminated. If the wall
being penetrated is constructed of non-
combustible material, i.e. masonry block or
concrete, a 7" diameter hole is acceptable.
Note:
a) The horizontal run of vent should have a 1/
4 inch rise for every 1 foot of run towards
the termination. Never allow the vent to run
downward. This could cause high temper-
atures and may present the possibility of a
fire.
b) The location of the horizontal vent termina-
tion on an exterior wall must meet all local
and national building codes, and must not be
blocked or obstructed. For External Vent
Terminal Locations, see diagram on page 9.
c) Snorkel Terminations:
For installations requiring a vertical rise on
the exterior of the building, 14-inch and 36-
inch tall Snorkel Terminations as shown in
Dia. 2 are available, as well as the standard
Riser Vent. Follow the same installation
procedures as used for standard Horizon-
tal Termination. NEVER install the snorkel
upside down.
Diagram 1
*Dia 2a & 2b: As speci-
fied in CGA B149 Instal-
lation Code. Local codes
or regulations may re-
quire different clearanc-
es.
NOTE: For Snorkel terminations in ABOVE
grade installations, follow national
or local code requirements.
Below Grade Snorkel Installation
If the Snorkel Termination must be installed
below grade, i.e. basement application,
proper drainage must be provided to pre-
vent water from entering the Snorkel Ter-
mination. Refer to Dura-Vent Installation
instructions for details.. Do not attempt to
enclose the Snorkel within the wall, or any
other type of enclosure.
4) Install wall penetration heat shield in the
center of the 9-1/2" round hole and attach
with wood screws. The four wood screws
provided should be replaced with appropri-
ate fasteners for stucco, brick, concrete,
or other types of sidings. Dia. 3.
5) If installing termination on a siding covered
wall, a vinyl siding standoff or furring strips
must be used to ensure that the termination
is not recessed into the siding. Dia. 3.
6) Take the Riser Vent terminal and separate
the Backing Plate from the Riser Vent Front
by removing 8 screws as shown in dia-
gram 4.
INSTALLATION
Diagram 2b
7) Install the Backing Plate into the wall pene-
tration heat shield and attach using 4
screws. Dia. 4.
8) Connect all pipe sections to unit and install
into wall:
a) Measure pipe length required and cut to
length. Hint: use the cut end of the 6-5/8" dia.
outer pipe at the vent terminal end.
b) Push the pipe sections completely together,
the minimum pipe overlap is 1-1/4". Secure
all outer pipe joints by using at least two
screws. Locate the screws at the bottom
of the pipe so that the screw heads are
hidden on the final installation. Apply seal-
ant "Mill-Pac" to inner pipe and high temp
silicone sealant or "Mill-Pac" to outer pipe on
every joint.
Hint: Apply sealant
to female end.