Common problems and solutions

Symptom

Common Causes

Possible Corrections

Rapid cycling — boiler

turns on and off frequently

Thermostat installed where drafts
or heat affect reading

Locate thermostat on inner wall away from
heat sources or cool drafts.

Heat anticipator in thermostat
adjusted incorrectly

Adjust thermostat per manufacturer’s
instructions.

Incorrect limit setting

Set limit according to system needs.
Maximum setting is 220˚F. Increase limit
setting to decrease cycling.

Insufficient water flow through
boiler

Check all valves to and from boiler. Return
to proper setting.

Confirm circulator size.

Frequent release of water

through relief valve

Expansion tank sized too small

Call qualified service technician to check
expansion tank operation and size.

Flooded expansion tank

Call qualified service technician to check
expansion tank operation.

Inoperative limit control

Call qualified service technician to replace
limit control.

Need to frequently add

makeup water

Leaks in boiler or piping

Have qualified service technician repair
leaks at once to avoid constant use of
makeup water. Makeup water can cause
mineral deposits which, in turn, can cause
boiler section failure. Do not use petroleum-
base stop-leak compounds.

Black water condition

Oxygen corrosion due to leaks in
boiler and piping

Have qualified service technician repair at
once. Keep pH of water between 7.0 to 8.5.