Appendix 5 (cont.) External OL Relay Applications

SPECIAL MOTOR APPLICATIONS

Multiple Motors
When more than one motor is connected downstream from the TE
Series
starter, the internal electronic overload protection cannot provide
proper protection of the individual motors. Codes require the use of
separate OLRs for each motor, which would need to be external
devices.

In these instances the TE Series Over Load protection should be turned
off, deferring protection to the separate OLRs. Care should be taken to
ensure that the External OLR is properly wired into the starter control
circuit to facilitate shutdown of the motor. The TE Series provides a
PTC input that can be wired to the NC auxiliary contact of the external
OLR so that a trip will still shut down the TE Series and be annunciated
on the display. Multiple OLRs would then be wired in series for the
same effect. See section 4.7.2.a for details on using the PTC input.

TE Starter

.

Bypass

Contactor

"BP"

Disconnect

or

Circuit

Breaker

Solid State

.

Over Load

.

MTR

1

G

R /

L1

T /
L3

S /

L2

U /

T1

W /

T3

V /

T2

External

Over Load 1

1

2

3

A1

A2

120VAC

CONTROL POWER

Start / Run

Command

TE...-BP Series

Control Wiring

TE-TB-1

(24VDC)

VMX-TB-2

MTR

2

External

Over Load 2

9

10

TE-TB-1

(PTC Input)

External

OL 1

External

OL 2