Toshiba 18 - 1250 A User Manual
Page 26
TE Series
Digital Solid State Soft Starters 18 – 1250A
19
4.2.5 Enabling the Dual Ramp and Jog Features
TB1 includes provisions for enabling the Dual Ramp and Jog functions
by using external contact closures. Both features use a common
+24VDC from Terminal # 7, however they can be used independently of
each other or together. See sections 5.6.2 and 5.6.3 for full function
descriptions and setup.
4.2.5.a
Dual Ramp Command
Closing a dry (voltage free) contact between TB1, terminals 6 and 7
will enable Ramp 2, and the TE Series starter will respond to the
settings for Ramp 2 in F015 - F018. If no contact closure is present,
the TE Series starter defaults to the Ramp 1 parameters (F011 –
F014). See Section 5.6.2.a for setup of the Dual Ramp Feature.
The Dual Ramp feature is useful in instances where the load
changes significantly. Example: a loaded or unloaded conveyor belt.
The characteristics for starting an unloaded conveyor can be
programmed for ramp 1. The characteristics for starting a loaded
conveyor can be programmed for ramp 2. Ramp 2 can also be
programmed for Full Voltage / Across-the-Line starting by setting
the ramp time to 0 and Current to 600%.
Dual Ramp is also useful in 2-speed motor applications. Simply use
an auxiliary contact from one of the speed contactors to select
Ramp 2 so that separate ramp profiles can be used.
4.2.5.b
Jog / Remote Command
Connecting a dry (voltage free) contact between TB1, Terminals 7
and 8 will enable the Jog feature. A Start command (Run Command
or Start button) is required to activate the Jog feature. See Section
5.6.3 for setup of the Jog Function.
The Jog feature can be used for tasks such as lining up machines
for blade or bit changes or inching belts along to check tracking.
This input is also used to change the function of the Serial
Communications port control through F068. For additional
information, see instructions of that function in section 5.6.11.
4.2.5.c
Using Both Commands
It may be useful to initialize the Ramp 2 and Jog command
simultaneously when jogging. If this is the case, terminals 6 and 8
can be jumped together and controlled with one contact closure to
Terminal 7 (the common 24VDC).
N C
JOG
RAMP2
PTC
OPTO
Figure 4.2.5.a:
Dual Ramp Connections
TB-1
RAMP 1 RAM P 2
6 7 8
N C
JOG
RAMP2
PTC
OPTO
Figure 4.2.5.b:
Jog Connections
TB-1
RUN JOG
6 7 8
N C
JOG
RAMP2
PTC
OPTO
Figure 4.2.5.c:
Dual Ramp / Jog Connections
TB-1
RAM P 2
RUN JOG
6 7 8