beautypg.com

Chapter 6 - start-up – Toshiba 18 - 1250 A User Manual

Page 69

background image

TE Series

Digital Solid State Soft Starters 18 – 1250A

62

Chapter 6 - Start-up

6.1

Basic Startup

Your new TE Series Soft Starter is factory preset for a wide variety of
applications and often can be used with minimal adjustment.

6.1.1

Three Step Process
1. Connect L1, L2, and L3 to power lines and
T1, T2, and T3 to motor.
2. Connect control wires and control power.
3. Program motor FLA (F001).

6.1.2

Start-up Parameters and Factory Defaults
Try the initial presets first and then adjust or enable the more
advanced features to meet your specific starting needs.

Fn #

Function

Name

Factory

Setting

Description / Factory Setting

F001

Motor Nameplate
FLA.

0

FLA must be programmed for
starter to function.

F002

Motor Nameplate
Service Factor

1.0 SF

Change only if necessary AND
motor is rated over 1.0SF

F003

Overload Class
During Start

Class 10

NEMA / UL Class 10

F004

Overload Class
During Run

Class 10

NEMA / UL Class 10

F005

Overload Reset

0 (Manual)

0 = Manual

F010 Ramp

Profile

1

Ramp 1 and Ramp 2 =
Voltage Ramp with Current Limit

F011

Initial Torque

60

60% Initial Voltage

F013

Ramp Time

10

10 Second Ramp (Ramp 1)

F014

Current Limit

350

350% of programmed FLA

F015 –
F018

Ramp 2 settings

---

Inactive unless Ramp 2 Input is
closed

F019 –
F052

Software protection
and control
features

---

Inactive unless selected

F053

Internal hardware
protection features

127 All

active

F054 –
F059

Timer and counter
value readouts

--- Read

only

F060

Aux Relay #1

1

Run / Stop

F061

Aux Relay #2

2

At-Speed / Stop

F062

Aux Relay #3

16

Any Trip

F063

Aux Relay Delay

0

No Delay

F065 –
F068

Communications

----

Not Used unless without optional
Comm Adaptor

F070

Parameter Lock

0

User password disabled

F071

Reset Function

0

Use to reset to default values

F073 –
F080

System settings
and time clock

---

User choice to adjust clock

F085 –
F093

Fault History

---

Read only

Table 6.1.2: Factory Presets