2 mstr function error codes, 3 mstr read example, 2 mstr inputs and outputs – Toshiba ICC MBP-100 User Manual
Page 67

66
15.1.2 MSTR Inputs and Outputs
Figure 38 indicates the inputs and outputs associated with MSTR instructions.
Activ ate MSTR Instruction
Instruction End - Error
Instruction End - No Error
MSTR Instruction
40050
(Control Block)
40100
(Data Area)
100
(# data registers)
Instruction Activ e
INPUTS OUTPUTS
Terminate MS TR Instruction
Figure 38: MSTR Inputs and Outputs
15.2 MSTR Function Error Codes
Table 8 indicates the error codes that may be output in the “4x+1” location of
the MSTR control block. These specific error codes can be generated by the
MBP-100. Additional error codes may be generated from other sources on the
Modbus Plus network.
Table 8: MSTR Error Codes
Error Code (Hex)
Meaning
3001
Slave device does not support the requested function
3002
Nonexistent slave device registers requested
3003
Invalid data value requested
15.3 MSTR Read Example
The following example demonstrates how to use the MSTR instruction to read 2
registers starting at register 1 from an MBP-100 located at Modbus Plus
network address 2.
1. Set up a ladder logic program as shown in Figure 37. Set the top portion
of the MSTR Instruction to 40050. This will be the starting address of the
MSTR Control Block. Set the control block registers to the following values: