Electrical data – Trane TWE200B User Manual
Page 32
32
SSP-PRC002-EN
Electrical
Data
Table ED-5— Unit Wiring With Electric Heat (Single Point Connection) — Air Handlers
Heater
Heater
To Use
Control
Minimum
Maximum
Model No.
kW Rating
1
with Unit
Stages
Circuit Ampacity
2
Fuse Breaker Size
2
BAYHTRL405A
3.47
1
9
15
BAYHTRL410A
6.92
TWE050AD
1
17
20
BAYHTRL415A
10.39
1
24
25
BAYHTRL425A
17.31
2
39
40
BAYHTRL405A
3.47
1
11
15
BAYHTRL410A
6.92
1
18
20
BAYHTRL415A
10.39
TWE075AD
1
26
30
BAYHTRL425A
17.31
2
41
45
BAYHTRL435A
24.22
2
56
60
BAYHTRL405A
3.47
1
12
15
BAYHTRL410A
6.92
1
19
25
BAYHTRL415A
10.39
TWE100AD, TWE100BD
1
27
30
BAYHTRL425A
20.78
2
42
45
BAYHTRL435A
24.22
2
57
60
BAYHTRM410A
6.94
1
21
30
BAYHTRM420A
13.83
TWE155BD
1
36
40
BAYHTRM430A
20.78
2
51
60
BAYHTRM450A
34.62
2
81
90
BAYHTRM410A
6.94
1
25
40
BAYHTRM420A
13.83
TWE200BD
1
40
50
BAYHTRM430A
20.78
2
55
60
BAYHTRM450A
34.62
2
85
90
1. kW ratings are at 400v for 3 phase, 400v air handlers
For other than rated voltage, ampacity =
Voltage
2
x Rated Capacity and kW =
Voltage
2
Rated kW.
(
Rated Voltage
)
(
Rated Voltage
)
2. Any power supply and circuits must be wired and protected in accordance with local codes.
3. Field wire must be rated at least 75°C.
4. Field wire must be rated at least 90°C.