Performance data — 60 hz (10–60ton) part load, Performance data — 60 hz, 10–60 ton) part load – Trane CG-PRC007-EN User Manual
Page 27

27
CG-PRC007-EN
Performance
Data — 60 HZ
Table PD-18— Part Load Data, ARI Points (10-60 Tons)
Entering Condenser Air Temperature (Degrees F)
Model
95
86.9
84.5
77.7
77.3
72.5
72.3
71.5
Tons Number
100% Load
86% Load
82% Load
71% Load
70% Load
62% Load
62% Load
61% Load
EER
10.0
—
—
—
—
—
—
—
10
CGA 120
2
Capacity (Tons)
8.7
—
—
—
—
—
—
—
KW
Input
10.5
—
—
—
—
—
—
—
EER
9.6
—
—
—
—
—
—
—
15
CGA 180
Capacity (Tons)
13.6
—
—
—
—
—
—
—
KW Input
16.9
—
—
—
—
—
—
—
EER
9.8
—
—
—
—
—
—
15.2
20
CGAF-C20
Capacity (Tons)
17.7
—
—
—
—
—
—
10.7
KW Input
21.6
—
—
—
—
—
—
8.5
EER
9.8
—
—
—
13.8
—
—
—
25
CGAF-C25
Capacity (Tons)
23.1
—
—
—
16.3
—
—
—
KW Input
28.3
—
—
—
14.2
—
—
—
EER
9.8
—
—
—
—
—
—
14.2
30
CGAF-C30
Capacity (Tons)
28.0
—
—
—
—
—
—
17.0
KW Input
34.3
—
—
—
—
—
—
14.4
EER
9.7
—
11.9
—
—
—
15.1
—
40
CGAF-C40
Capacity (Tons)
34.5
—
28.4
—
—
—
21.4
—
KW Input
42.7
—
28.6
—
—
—
17.1
—
EER
9.7
11.3
—
13.5
—
—
—
—
50
CGAF-C50
Capacity (Tons)
43.0
37.2
—
30.6
—
—
—
—
KW Input
53.2
39.4
—
27.2
—
—
—
—
EER
9.7
—
11.9
—
—
15.2
—
—
60
CGAF-C60
Capacity (Tons)
55.4
—
45.7
—
—
34.6
—
—
KW Input
68.6
—
45.9
—
—
27.3
—
—
Table PD-18 Continued — Part Load Data, ARI Points (10-60 Tons) Continued
Entering Condenser Air Temperature (Degrees F)
Model
66.2
65.3
57.4
55
Tons Number
52% Load
51% Load
37% Load
32% Load
EER
13.5
—
—
—
10
CGA 120
Capacity (Tons)
4.6
—
—
—
KW
Input
4.1
—
—
—
EER
13.5
—
—
—
15
CGA 180
Capacity (Tons)
7.1
—
—
—
KW Input
6.2
—
—
—
EER
—
—
—
—
20
CGAF-C20
Capacity (Tons)
—
—
—
—
KW Input
—
—
—
—
EER
—
15.3
—
—
25
CGAF-C25
Capacity (Tons)
—
11.7
—
—
KW Input
—
9.1
—
—
EER
—
—
—
—
30
CGAF-C30
Capacity (Tons)
—
—
—
—
KW Input
—
—
—
—
EER
—
—
—
17.6
40
CGAF-C40
Capacity (Tons)
—
—
—
10.9
KW Input
—
—
—
7.4
EER
—
—
17.0
—
50
CGAF-C50
Capacity (Tons)
—
—
15.9
—
KW Input
—
—
11.2
—
EER
—
—
—
18.3
60
CGAF-C60
Capacity (Tons)
—
—
—
17.8
KW Input
—
—
—
11.7
(10–60 Ton)
Part Load
Notes:
1. Rated in accordance with ARI Standard 550/590-98
- 44 Degrees leaving chilled water temperature
- Constant Evaporator waterflow as determined at full load operation, 95 F ambient, and 10F evaporator temperature drop.
- Entering ambient temperature based on 55F for loads below 33%
- Entering ambient temperature based on 0.60(%load)+35 for loads above 33%
- EER- Energy Efficiency Ratio ( Btu/Watt-hour). Power inputs include compressor, condenser fans and control power.
2. Single phase CGA120B1 model should be re-rated at all operating points using the following factors: 1.08 x KW, 0.92 x EER