Vf-mb1/s15 communication parameters – Toshiba Tosvert VF-MB1/S15 User Manual

Page 10

background image

E6581738

- 8 -

2.3.

VF-MB1/S15 Communication parameters

In a network, VF-MB1/S15 (PDP003Z) serves as a PROFIBUS slave device. PDP003Z
configuration is set by the following parameters.

Parameter

Function

Adjustment range

Default

setting

c150

PDP003Z

Station address

2 to 126
The station address "126" cannot exchange data.

126

c151

PDP003Z

Baud rate Monitor

0: 12 Mbit/s
1: 6 Mbit/s
2: 3 Mbit/s
3: 1.5 Mbit/s
4: 500 kbit/s
5: 187.5 kbit/s
6: 93.75 kbit/s
7: 19.2 kbit/s
8: 9.6 kbit/s

-

c152

PDP003Z

Profile Monitor

0:Telegram 1 (PROFIdrive)
1:Telegram 100 (Vender Spec. 1)
2:Telegram 101 (Vender Spec. 2)
3:Telegram 102 (Vender Spec. 3)

-

c154

JOG1 Frequency

(STW.8)

0.0 to 20.0Hz

5.0Hz

c155

JOG2 Frequency

(STW.9)

0.0 to 20.0Hz

5.0Hz

c156

Tmax

(ZSW.8)

0.1 to 60.0s

10.0s

c157

Tolerance

(ZSW.8)

0.1 to 99.0%

50.0%

c100

Communication error

detection delay time

0.0 to 100.0 sec

0.0

c101

Drive operation at the

communications

loss action

(Network wire breaks)

0: Stop and Communication release *

(follows

cmod

and

fmod

setting)

1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
5: Preset speed operation command

(Operating at the preset speed operation frequency
set with

c102

)

4

c102

Preset speed

operation selection

0: None
1 to 15: Preset speed (

sr1

-

sr7

,

f287

-

f295

)

0

c103

**

Communication

time-out condition

selection

0: Disconnection detection
1: When communication mode enable (Both

cmod

and

fmod

are set CANopen or COM option)

2: 1+Driving operation

1

f899

Network option

reset setting

0: None
1: Resetting the PDP003Z and the drive

0

fd67

PDP003Z versioon PDP003Z firmware version

(ex. 0x1101 means "V1.01")

-

*

Do not set at VF-MB1 V1.00.

**

It is necessary to enable "Watchdog" function with the configurator.

*** When the parameters are changed or to reset

err8

, the power must be cycled (or set

f899

to 1).

After reset, the parameter changes become effective.

Set 1

to

f899

by the PROFIBUS communication might not be able to be set.

**** When

fmod

or

cmod

is set to “Communication option”, VF-MB1/S15 drives without

Net Reference

(STW Bit 13) or

Net Control

(STW Bit 12) at PROFIdrive.

Please note that drive keeps driving when the communication is lost if

1

(None) is set to

the parameter

c101

(Drive operation at the communications loss action).

Caution