Toshiba AS311 User Manual
Page 37

User’s
Manual
35
4. Register Configuration
CH1 time-out check (25) and
CH2 time-out check (89)
The address 25 (for channel 1) and the address 89 (for channel 2) store the time-out
check times. If the time between each receiving character exceeds the specified time-out
check time, it becomes the receiving time-out error. The default setting is 1 second.
To change the setting, write the desired data into this address then write the hot reset
command into the Command 1 (12). See section 5.7 for this procedure.
F E D C B A 9 8 7 6 5 4 3 2 1 0
25 or 89
Time-out check time
Bit F-0
Time-out check
time
Stores the time-out check time (0.1 s units).
Valid data range is 1 to 600 (0.1 to 60 s). If 0 or more
than 600 is specified, the time-out check will not work.
Initial value at power on is 10 (1 s).
- MK4007GAL (9 pages)
- DVD-ROM DRIVE SD-M1712 (16 pages)
- OIS40R (2 pages)
- IVP8 (71 pages)
- MK8016GSG (2 pages)
- Tecra 061215 (38 pages)
- G9 ETB006Z (1 page)
- SD-R2412 (12 pages)
- OIS50 (2 pages)
- PCX1000 (18 pages)
- MK6026GAX (11 pages)
- Entone 95-810500-00 (14 pages)
- SD-R1002 (16 pages)
- 512E (1 page)
- T2N (272 pages)
- MK3004GAH (9 pages)
- AR-B1375 (69 pages)
- AUXILIARY CABINET 431B (64 pages)
- MK1016GAP (11 pages)
- MK1234 (4 pages)
- A305 (3 pages)
- 1.8-INCH HARD DISK DRIVE MK6006GAH (9 pages)
- MK3006GAL (153 pages)
- AF 512E (2 pages)
- MK8007GAH (9 pages)
- BCN002Z (16 pages)
- DRIVE MK6022GAX (11 pages)
- MK2003GAH (9 pages)
- MK6006GAH (157 pages)
- XM-6802B (15 pages)
- Parani UD100 (1 page)
- V.90 (102 pages)
- MK4025GAS (11 pages)
- MK5002MPL (9 pages)
- SD-R1512 (17 pages)
- Rockbox F Series (177 pages)
- (HDD2188) (11 pages)
- Low Voltage Motors VR Series (2 pages)
- MK1214GAP (11 pages)
- SD-M2012C (16 pages)
- 480082-D0 (9 pages)
- SD-C2712 (12 pages)
- HDD2188 MK8025GAS (11 pages)
- Electromagnetic Flowmeter Converter TIC-LF232A (8 pages)
- P000233790 (53 pages)