beautypg.com

Truly designed for, Current voltage, Small footprint – Toshiba QX7 Series User Manual

Page 3: E: 60 hz, 113 hz

background image

Total Harmonic Distortion (THD) can be caused by multiple factors including: computers,

fluorescent lights, copiers, and six-pulse drives. With Toshiba’s patented 18-Pulse

Autotransformer design, the QX7 removes distortion that would normally be generated by

a six-pulse drive.

Meets IEEE-519 Guidelines without Adding Filters

Produces a Ripple-Free Voltage on DC Bus

Clean Sinusoidal Input Current Waveform

Up to 60% Reduction in Transformer Losses

Truly Designed for

INPUT CURRENT HARMONICS

0

10

20

30

40

50

60

70

80

90

100

5

7

11

13

17

19

23

25

29

31

35

37

41

43

47

49

HARMONIC NUMBER

% OF FUNDAMENTAL

6-Pulse (Typical)

18-Pulse HX7

e: 60 Hz

@

: 113 Hz

Ch1

500mV

Ch2

5.00mVΩ

M2.00ms

Ch1

10mV

Current

Voltage

Small Footprint

The high cost of real estate and constraints

of existing facilities make size an important

consideration in drive selection.

100” Height and 24” Depth on All Sizes

Integrated Phase-Shifting Autotransformer

Saves Real Estate on New Designs

Easy Replacement for Older Drives in

Existing Facilities

(Addition of a bypass option will increase enclosure size.)

!

$

7'

3(

2%

6

"

#

$

(

'

&

%

!

#

$

%

&

'

(

%

INPUT CURRENT HARMONICS