beautypg.com

Component air pressure drops, Installation – Trane RT-SVX19A-E4 User Manual

Page 17

background image

Installation

17

RT-SVX19A-E4

Component air pressure drops

Table 7 - YKD/YKH Pressure drop through accessories

Filter

Filter

Economizer Economizer

Airflow

EU2/G2

EU4/G4

100%

outside air

100%

return air

YKD/YKH 155

6800

13

27

8

6

7650

16

30

10

7

8500

19

34

12

8

9350

22

37

14

9

10200

26

40

16

10

YKD/YKH 175

7870

17

30

10

7

8860

21

34

12

8

9850

25

38

15

9

10840

30

43

17

11

11830

35

47

20

12

YKD 200

8970

12

26

29

6

10090

15

30

37

8

11210

19

33

45

9

12330

23

37

55

11

13450

27

41

65

13

YKH 200

8970

11

23

33

6

10090

14

26

41

8

11210

17

29

51

9

12330

20

33

61

11

13450

23

36

72

13

YKD 250

11280

18

32

46

10

12690

24

36

58

12

14100

29

41

71

14

15510

36

46

86

17

16920

43

51

102

19

YKH 250

11280

17

30

52

10

12690

21

34

65

12

14100

26

38

80

14

15510

31

43

96

17

16920

36

47

114

19