Toshiba HHGP1 User Manual
Page 28
26
6 F 2 S 0 7 3 8
Surge Immunity
IEC61000-4-5,
EN61000-4-5
1.2/50
µs surge applied to PSU terminals in common/differential
modes: 2kV/1kV (peak)
Conducted and
Radiated Emissions
EN55022 Class A
Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions:
30 to 230MHz: <30dB
230 to 1000MHz: <37dB
Power Frequency
Magnetic Field
IEC61000-4-8,
EN61000-4-8, Class 4
Field applied at 50Hz with strengths of:
30A/m continuously,
300A/m for 1 second.
Pulsed Magnetic Field IEC61000-4-9,
EN61000-4-9, Class 5
6.4/16
µs magnetic pulses (positive and negative) applied with
magnitude 1000A/m.
Damped Oscillatory
Magnetic Field
IEC61000-4-10,
EN61000-4-10, Class 5
Oscillation frequencies of 0.1MHz and 1MHz applied with
magnitude 100A/m.
European Commission Directives
89/336/EEC
Compliance with the European Commission Electromagnetic
Compatibility Directive is demonstrated according to generic
EMC standards EN50081-2 and EN50082-2.
73/23/EEC
Compliance with the European Commission Low Voltage
Directive is demonstrated according to generic safety
standards EN61010-1 and EN60950.