beautypg.com

Notice, Caution – The New Yorker Store Cast Iron-Oil Fired Boiler CL User Manual

Page 13

background image

1

and oxygen into the boiler. These contaminants

greatly accelerate corrosion of the cast iron

boiler sections.
i. Assure that all system radiators, piping and

vents are absolutely leak tight.

• When a steam boiler is installed in an

existing system, ALL air vents should be

replaced at the same time. This assures

that the new boiler will not be

compromised by existing system leaks.

• If the system contains hidden supply or

return piping (hidden behind walls, buried

in concrete, etc.) pressure test this piping

to assure there are no leaks.

ii. Repair any leaks in the system.
iii. Install accurate water meter on the fresh

water supply to the boiler.

NOTICE

Do not use softened water in steam boilers.

Accelerated boiler corrosion will result. Tie in

fresh water supply to the boiler upstream of a

water softener.

4. OXYGEN CONTAMINATION:

a. There are many possible causes of oxygen

contamination such as:
i. Addition of excessive make-up water as a

result of system leaks.

ii. Absorption through open tanks and fittings.
iii. Oxygen permeable materials in the

distribution system.

b. In order to insure long product life, oxygen

sources should be eliminated. This can be

accomplished by taking the following measures:
i. Repairing system leaks to eliminate the need

for addition of make-up water.

ii. Eliminating open tanks from the system.
iii. Eliminating and/or repairing fittings which

allow oxygen absorption.

iv. Use of non-permeable materials in the

distribution system.

v. Isolating the boiler from the system water by

installing a heat exchanger.

See Section V, Paragraph B, Step 3 for additional

details.

CAUTION

Oxygen contamination of the boiler water

will cause corrosion of iron and steel boiler

components, and can lead to boiler failure. New

Yorker's Standard Warranty does not cover

problems caused by oxygen contamination of

boiler water or scale (lime) build-up caused by

frequent addition of water.

H.

CONNECT SUPPLY AND RETURN PIPING TO

HEATING SYSTEM.
1. CLEARANCES — Steam and hot water pipes shall

have clearances of at least ½” from all combustible

construction.

2. WATER BOILER

a. For Forced Circulation HOT WATER HEATING.

See Figure 9. Consult I=B=R Installation and

Piping Guide No. 200.

b. Use a boiler water bypass if the boiler is to be

operated in a system which has a large volume

or excessive radiation where low boiler water

temperature may be encountered (i.e. converted

gravity circulation system, etc.).

Install a pipe tee between the circulator and

boiler return along with a second tee in the

supply piping as shown in Figure 9. The bypass

should be the same size as the supply and return

lines. Locate valves in the bypass and supply

outlet as illustrated in Figure 9 for regulation

of water flow to maintain higher boiler water

temperature.

Set the by-pass and boiler supply valves to a half

throttle position to start. Operate boiler until the

system water temperature is a normal operating

range.

Adjust the valves to provide 180° to 200°F

supply water temperature. Opening the boiler

supply valves will raise the system temperature,

while opening the bypass valve will lower the

system supply temperature.

c. If this boiler is connected to heating coils located

in air handling units where they may be exposed

to refrigerated air the boiler piping must be

equipped with flow control valves to prevent

gravity circulation of boiler water during the

operation of the cooling system.

d. If this boiler is used in connection with

refrigeration systems, the boiler must be installed

so that the chilled medium is piped in parallel

with the heating boiler using appropriate valves

to prevent the chilled medium from entering

the boiler, see Figure 10. Also consult I=B=R

Installation and Piping Guides.

e. A hot water boiler installed above radiation level

must be provided with a low water cutoff device

as part of the installation. See Section VIII, Low

Water Cut-Off for additional details.

3. STEAM BOILER

a. For Recommended STEAM BOILER PIPING

refer to Figure 11. Also, consult I=B=R

Installation and Piping Guides.

b. Evaluate the Existing Steam System.
The single most important factor in determining

the expected life cycle of a steam boiler, is

the amount of fresh water added to the boiler

during operation. Fresh water brings minerals