beautypg.com

Therma-Stor Products Group HI-E Dry Vehere User Manual

Page 5

background image

5

www.thermastor.com • [email protected]

Toll-Free 1-800-533-7533

Controller

If the Vehere is to be located in a remote location outside

the pool or spa area, mounting of the humidity sensor in the

space to be conditioned is necessary. If the humidity sensor

is not located in the conditioned space, the Vehere will not

operate properly.

IMPORTANT: Locate the humidity element on an inside wall, free
from drafts, out of direct sunlight, and where the element is not
exposed to excessive vibration. Be careful not to drop the unit.
Mount the wall mount element at a height of 4 to 6 feet (1.2 to
1.8 m) above the floor.

To mount the HI-E DRY Vehere dehumidistat on a wall for

remote application, first remove the cover from the controller

by lifting the side of the controller cover over the catch tabs

on both sides. The cover comes off easily.

Hold the unit to the surface you would like to mount it on. You

will need to mark the locations for two screw holes and one

square knockout to accommodate wires and the devices wire

guard. The wire-guard tabs fit inside the wall. (See Fig. 6, 7)

Once marked, drill a 1/8” hole for each mounting screw

location and tap the provided anchor mount into the hole.

Use the provided screws to then mount the humidity

control to the wall. Route the wiring through the hole you

have created and connect wires according to the directions

found in this manual. Replace plastic housing.

3.3 Electrical Requirements

The Vehere can be plugged into any grounded 20 Amp circuit.

At 80°F, 60% RH, it draws 12 Amps. A dedicated 20 Amp

circuit is recommended.

3.4 Condensate Removal

Condensate drains by gravity via the clear hose extending

from the unit. Route the 4’ drain hose to a floor drain. Use

care to keep the hose as flat to the floor as possible. Keep

the hose away from walk ways if possible. Excessive humps

or kinks will prevent proper drainage. If the Vehere is located

too far from a floor drain for the attached hose to reach,

inexpensive 1/2” PVC pipe can be used to extend it. It is

commonly available in 10’ lengths from building supply,

plumbing and hardware stores. It will slide tightly inside the

end of the drain hose. If more than one length of pipe is

required, they can be joined with a short piece cut from the

end of the drain hose.

3.5 Ducting

3.5A Ducting kit
The factory installation kit includes two twelve-inch collars

to allow ducting to be attached to the inlet and outlet of

the Vehere. The 12” collar with three tabs can be attached

via the holes provided in the front of the unit, and the 12”

flanged collar can be affixed to the top opening. S (See Fig. 8)

3.5B Ducting for Dehumidification
Ducting the Vehere as mentioned requires consideration of

Figure 6: Mark mounting

holes as indicated by arrows.

Figure 7: Control

connection wires.

Figure 8: Tabbed duct collar is installed around the exhaust

outlet. The flanged duct collar is installed around the intake

opening.

Tabbed duct collar

Flanged duct

collar