beautypg.com

Optima 45 - 3 – Optima Company Optima 45 - 3 User Manual

Page 21

background image

Optima 45 - 3

21

VENTING - HORIZONTALLY USING SIMPSON DURA-VENT DIRECT VENT SYSTEMS

INSTALLATION PROCEDURES FOR SIMPSON DURA-VENT DIRECT VENT SYSTEM

Fig. 1

Fig. 2

Fig. 3

5. Mark the wall with an 11” (279 mm) x 10” (254 mm) hole.

See termination framing on page 22. The center of the hole
should line up with the centerline of the horizontal pipe. Cut
and frame the 11” (279 mm) x 10” (254 mm) hole in the ex-
terior wall where the vent will be terminated. If the wall be-
ing penetrated is constructed of non-combustible material,
(I.E. a masonry block, or concrete) a hole with zero clear-
ance is acceptable. NOTE: The horizontal run of vent must
be level, or have a ¼” (6 mm) rise for every 12” (305 mm) of
run towards the termination. Never allow the vent to run
downward. This could cause high temperatures and may
present the possibility of a fire. ALSO: The location of the
horizontal vent termination on an exterior wall must meet
local and national building codes, and must not be blocked
or obstructed. For Allowable Termination Locations see
page 11 in this manual.

6. Position the Horizontal Vent Termination in the center of the

square hole (arrow on the vent cap should be facing UP),
and run a bead of non-hardening sealant around the outside
edges of the termination, so as to make a seal between the
termination and the wall. Finish attaching the termination
cap to the wall with the four wood screws provided with the
termination cap. NOTE: The four wood screws provided
should be replaced with the appropriate fasteners for
stucco, brick, concrete or other types of siding. For buildings
with VINYL SIDING, a Vinyl Siding Standoff should be in-
stalled between the vent cap and the exterior wall. Attach
the Vinyl Siding Standoff to the Horizontal Termination Cap
by bolting the flat portion of the Vinyl Siding Standoff (Fig.1)
so that an air space will exist between the wall and the Vent
Termination.

7. Locate and slide the Wall Thimble Cover over the vent pipe.
8. Slide the appliance and vent assembly towards the wall,

carefully inserting the vent pipe into the vent cap assembly.
It is important that the vent pipe extend into the vent cap
sufficient distance so as to result in a minimum pipe overlap
of 1 ¼” (31 mm). Secure the connection between the vent
pipe and the vent cap by attaching the two sheet metal
strips extending from the vent cap assembly into the outer
all of the vent pipe. Use the two sheet metal screws pro-
vided to connect the strips to the pipe section. Bend any re-
maining portion of the sheet metal strip back towards the
vent cap, so it will be concealed by the Wall Thimble Cover.
(Fig. 2)

9. Slide the Wall Thimble Cover up to the wall surface and at-

tach to the wall with wood screws. (Fig. 3)