NOTE:

Galvanized pipe is desirable above the roofline
due to its higher corrosion resistance. Continue
to add pipe sections throughout the flashing until
the height of the vent cap meets the minimum
height requirements specified in Fig. 5 or local
codes.

For steep roof pitches, the vertical height must
be increased. A poor draft, or down drafting can
result in high wind conditions, trees or neighbor's
roof lines. In these cases increasing the height
may solve a drafting problem. REMEMBER to
check that you are within the maximum vertical
height restrictions, and are placing the appropri-
ate vent restrictors as outlined in the venting
chart within this manual.

Any storage spaces or closets which the vent
must pass through must be enclosed.

Flat to 7/12

2 Feet

0.61 Meters

Over 7/12-8/12

2 Feet

0.61 Meters

Over 8/12-9/12

2 feet

0.61 Meters

Over 9/12-10/12

2.5 Feet

0.76 Meters

Over 10/12-11/12

3.25 Feet

1.00 Meters

Over 11/12-12/12

4 Feet

1.22 Meters

Over 12/12-14/12

5 Feet

1.52 Meters

Over 14/12-16/12

6 Feet

1.83 Meters

Over 16/12-18/12

7 Feet

2.13 Meters

Over 18/12-20/12

7.5 Feet

2.29 Meters

Over 20/12-21/12

8 Feet

2.44 Meters

Roof Pitch

Minimum Vent Height

Vertical Termination
Cap

Storm Collar

Flashing

Ceiling Firestop

Round Support
Box/wall Thimble

Length of Pipe

Length of Pipe

SDA-U adaptor

VENTING - VERTICAL TERMINATION USING SIMPSON DURA-VENT PIPE

Simpson Dura-Vent venting

components are listed on page 21

Typical Vertical venting

configuration using Simpson

Dura-Vent Direct Vent System

Fig. 5

H-represents vent

height

H