beautypg.com

Omega Engineering DAQ-12 User Manual

Page 13

background image

The final stage of the A/D converter circuit is the A/D converter IC. The converter must be
configured for unipolar or bipolar input voltages as shown in Figure 2-3. When configured
for unipolar operation, the analog input multiplied by the gain setting must be in the range of
0 volts (analog ground) to +10 volts. When configured for bipolar operation, the analog
input multiplied by the gain setting must be in the range of -5 volts to +5 volts.

Bipolar

1 2 3

4 5 6

J6

Unipolar

1 2 3

4 5 6

J6

Figure 2-3. Jumper J6 Configuration

WARNING: The user must ensure that the maximum input voltage multiplied by the
amplifier gain does not exceed the range of 0 to +10 volts for unipolar operation or -5 to
+5 volts for bipolar operation.

Although the A/D converter produces 12-bit digital 'codes' to represent the input voltage, the
DAQ-12 converts these 'codes' into standard 16-bit signed integer values before returning
them to the PC. When the A/D converter is configured for unipolar operation, the DAQ-12
returns values in the range of 0 to 4095. When configured for bipolar operation, values in the
range of -2048 to +2047 are returned.

In order to calculate the actual input voltage from the value provided by the DAQ-12, the user
must know the configuration (unipolar / bipolar) and the gain setting used to acquire the
data. Given this information, the input voltage can be calculated using the following
equations:

Unipolar mode:

input =

*

CODE

4096

10V

GAIN

Bipolar mode:

input =

*

CODE

2048

5V

GAIN

DAQ-12 Users Manual 13