Sample Installation Diagram

NOTE:
-

Damage to the Indirect Pool Heater due to improper water chemistry is not covered under the warranty

-

Chlorine feeder must be installed after (downstream of) the Indirect Pool Heater and be installed with an
anti-siphoning valve to prevent chlorine from backing up into the Indirect Pool Heater.

-

This is only a conceptual drawing. A qualified installer must determine whether this system setup
will work in each application. Installer must also ensure compliance with code requirements.

1.
2.

Indirect Pool Heater

3.
4.
5.
6.

Gate valve

7.

Check valve

8.
9.

10.

Flow switch

11.

Thermometer
Drain valve
Filter
Pool/Spa Pump

Bypass valve

POOL WATER FLOW

POOL WATER FLOW

BOILER WATER FLOW

BOILER WATER FLOW

6

Thermostat or Aquastat

3

1

4

6

2

2

9

8

5

7

10

2

2

11

11

Union

TO BOILER CONTROL

12.

Boiler Pump

11

11

3

12

On the pool side the flow may be variable either due to

variable speed pumps or changes in the pressure drop

through the filtration system. These variances can be

accommodated by installing a 2lb spring loaded check

valve in the bypass line along with a manual valve (see

Figure 2 for details).

On model sizes 045 to 495, the check valve will con-

trol bypass flow by directing all flow through the

exchanger under low flow conditions, and avoiding

excessive flow through the heat exchanger under high

flow conditions. On 995 models the 2lb check valve

does not provide enough resistance to direct adequate

flow through the heat exchanger, and must be aug-

mented by using the manual valve to throttle flow to

provide approximately 6 to 15 ft of head across the

995 exchanger.

Controls

The Indirect Pool Heater must be installed with tem-

perature and flow controls to protect the heat

exchanger and control water temperature supplied to

the pool or spa. The return from the pool/spa must be

controlled at the inlet to the Indirect Pool Heater by a

thermostat set to the desired temperature for the

pool/spa, with the maximum recommended operating

temperature of 104°F. A second temperature control

must be installed in the outlet piping of the Indirect

Pool Heater to limit pool/spa supply temperatures to

140°F maximum. In addition to the temperature con-

trols, a flow switch should be installed in the pool/spa

supply line to prove adequate flow through the heat

exchanger. All three of these controls must be satis-

fied to provide a call for heat to the heat source.

Chlorine feeders or salt water

generators

The chlorine feeder or salt water generator (with CR24

exchangers only) must be installed after (downstream

of) the Indirect Pool Heater and be installed with an

anti-siphoning valve to prevent chlorine from backing

up into the Indirect Pool Heater. During periods of high

or fluctuating chlorine levels the Indirect Pool Heater

must be isolated from the system by closing the isola-

tion valves, protecting the unit from chemical damage.

CAUTION:

Operating control, high limit and flow

switch are NOT part of the Indirect Pool Heater.

These items must be supplied separately.