Installation, Exterior vent terminal locations – Regency ULTIMATE U37-LP1 User Manual

Page 8

background image

8

U37-1 Regency

®

ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove

INSTALLATION

EXTERIOR VENT TERMINAL LOCATIONS

A=

Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm)

B=

Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm)

C=

Clearance to permanently closed window *(min. 12"/30cm)

D=

V

ertical clearance to ventilated soffi

t located above the terminal within a horizontal

distance of (24"/60cm) from the centerline of the terminal (min. 22"/55cm) check with

local code.

E=

Clearance to unventilated soffi

t

(min.

12"/30cm)

F=

Clearance to outside corner (12"/30cm)

G= Clearance

to

inside

corner

(12"/30cm)

H=

Not to be installed above a meter/regulator assembly within

(3'/90cm) horizontally from the centerline of the regulator

.

J=

Clearance to service regulator vent outlet *(min. 36"/90cm)

K=

Clearance to non-mechanical air supply inlet to building

or the combustion air inlet to any other appliance *(12"/30cm) #(9"/23cm)

L=

Clearance to a mechanical air supply inlet *(min. 72"/1.8m)

#3' (91cm) above if within 10' (3m) horizontally

.

M=

**Clearance above paved sidewalk or a paved driveway located

on public property *(min. 84"/2.1m)

N=

Clearance under veranda, porch, deck, or balcony *(min.

12"/30cm)***

Note: *

As specifi

ed in CGA

B149 Installation Code. Note: Local codes or regulations may require dif

ferent clearances.

**A

vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings a

nd serves both dwellings.

***Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl

oor

.

# In accordance with the current

ANSI Z223.1/NFP

A

54, National Gas Code