beautypg.com

Installation, Aeration adjustment, Log set installation – Regency ULTIMATE U37-LP1 User Manual

Page 20: Gas connection, High elevation

background image

20

U37-1 Regency

®

ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove

AERATION

ADJUSTMENT

The burner aeration is factory set but may need
adjusting due to either the local gas supply, air
supply or altitude.

Natural Gas: 1/4" open

Propane:

3/8" open

The aeration adjustment gears are located on
the right side of the burner box and can be ac-
cessed from the side or from the front when the
louvers are removed.

To adjust the aeration: use the allen key to turn
the turning gear which will adjust the air shutter.
Open the air shutter for a blue fl ame or close it
for a yellower fl ame. The factory setting should
be suffi cient for most installations.

Clockwise to open,

counter-clockwise to close.

Caution: Carbon will be produced if the air
shutter is closed too much.

Note: Any damage due to carboning result-

ing from improperly setting the aera-
tion controls is NOT covered under
warranty.

Note: Aeration Adjustment should only be

performed by an authorized Regency

®

Installer at the time of installation or
service.

LOG SET

INSTALLATION

Read the instructions below carefully and
refer to the diagrams. If logs are broken
do not use the unit until they are replaced.
Broken logs can interfere with the pilot
operation.

The gas log kit contains the following:

a) 02-65 Rear

Log

b) 02-56 Middle Left Log
c) 02-44 Front Left Log
d) 02-46 Left

Top

Log

e) 02-45 Front Right Log
f) 02-47 Center

Log

g) 02-48 Middle

Right

Log

h) Embers

902-151

i) Lava

902-154

Embers

Embers

The "02" refer numbers (i.e. 02-65) are

molded into the rear of each log.

1) Carefully remove the logs from the box and

unwrap them. The logs are fragile, handle
with care - do not force into position.

2) Sprinkle the embers on the left and right

sides of the fi rebox base.

GAS CONNECTION

The gas connection is a 3/8" NPT 90

o

elbow.

The gas line can be rigid pipe or to make in-
stallation easier, use a listed fl exible connector
and/or copper tubing if allowed by local codes.
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
codes. For USA installations follow local codes
and/or the current National Fuel Gas Code,
ANSI Z223.1.

When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so
that gas lines can be easily disconnected for
burner and/or valve servicing. Flare nuts for
copper lines and fl ex connectors are usually
considered to meet this requirement.

Important: Always check for gas leaks with a
soap and water solution or gas leak detector.
Do not use open fl ame for leak testing.

Note: Prior to any pressure testing of

the gas supply piping system
that exceeds test pressures of
1/2 psig, this appliance must be
disconnected from the piping
system. If test pressures equal to
or less than 1/2 psig are used then
this appliance must be isolated
from the piping system by clos-
ing its individual manual shut-off
valve during the testing.

HIGH ELEVATION

This unit is approved in Canada for altitude 0 ft.
to 4500 ft. (CAN/CGA-2.17-M91). For Natural
Gas installations above 4500 ft. follow current
CAN/CGA-B149.1.

System Data - U37

For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes:
Natural Gas Propane
Burner

#37

#52


Max. Input Rating

30,000 Btu/h

Min. Input Rating

15,000 Btu/h

Supply Pressure
Natural Gas

min. 5.0" w.c.

Propane

min.

12.0"

w.c.

Manifold Pressure
Natural Gas

3.8" +/- 0.2" w.c.

Propane

11" +/- 0.2" w.c.

INSTALLATION