NOTE: To avoid water damage or scalding due to valve
operation, drain pipe must be connected to valve outlet
and run to a safe place of discharge. Drain pipe must
be the same size as the valve discharge connection
throughout its entire length and must pitch downward
from the valve. No shut-off valve shall be installed
between the relief valve and the drain line. Valve lever
should be tripped at least once a year to ensure that
waterways are clear.

ELECTRICAL WIRING

NOTE: If it is necessary to replace any of the original
wiring, it must be replaced with 105°C wire or its
equivalent, except all black wire must be replaced with
150°C wire or its equivalent.

CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation after
servicing.

DANGER - SHOCK HAZARD - Make sure electrical
power to the heater is disconnected to avoid potential
serious injury or damage to components.

MILLIVOLT SYSTEM

The Millivolt System Residential Heater is equip-

ped with a self-generating electrical system in which the
electric current is provided by means of a pilot generator.
No external electrical connections are required.

When installing a remote switch, do not exceed 10 feet

of wiring from the heater. Use 18 gage stranded wire.

ELECTRONIC INTERMITTENT IGNITION
DEVICE SYSTEM (IID)

NOTE: When the electrical hookup to the heater
requires both 24V and 115V or 240V, each input
voltage must be isolated in separate conduit.

The Electronic Intermittent Ignition Device automati-
cally lights the pilot and main burners upon a call for
heat. The heater is supplied with a dual voltage trans-
former for 120V or 240V input power hookup. Heaters
are factory wired for 240V power supply.

Fig. # 8929.1

17

NOTE: IID PROPANE UNITS ONLY: Heater is equipped
with an electronic ignition device with a 100% safety
lockout feature. If the heater fails to start or lockout,
reset the ignition device by interrupting the power to the
heater for 60 seconds.

CAUTION: If service replacement of the electronic
ignition device is required, replace only with a 100%
safety lockout device with 90 second trial for pilot
ignition.

HONEYWELL
INTERMITTENT
IGNITION
DEVICE