TEMPERATURE CONTROL

36

147 Hi/Low Models (CTX Thermostat)

Set Point Adjustment:

• Press the ‘set’ button,

SE.1 will be displayed for twelve (12) seconds.

• Press the ‘set’ button again,

The current set point value will be displayed.

• Press the down button (

/PRG) to decrease the set point or the up button (

▲/

ALM) to increase the set point.

• Once the required set point is selected, press the ‘set’ button to save the setting,

SE.1 will be re-displayed for twelve (12) seconds.

• Press the up button (

▲/

ALM),

SE.2 will be displayed.

• Press the ‘set’ button,

The current set point for Low Fire will be displayed.

• Press the down button (

/PRG) to decrease the set point or the up button (

▲/

ALM) to increase the set point.

• Once the required set point is selected, press the ‘set’ button to save the setting,

SE.2 will be re-displayed

• Wait 12 seconds,

The current temperature in the water heater will now be displayed and programming complete.

The recommended set points for SE.1 and SE.2 are 82°C and 75°C respectively for a heating system. However, it
may be necessary to increase SE.2 if there is an unacceptable variation in room temperature.

Differential Adjustment:

• Press and hold the down button (▼/PRG) for at least 5 seconds,

“‘E0” will be displayed.

• Press the up button (▲/ALM) until “E5.1” (differential setting for SE1).is displayed
• Press the ‘set’ button,

The current differential value will be displayed.

• Press the down button (▼/PRG) to decrease the differential or the up button (▲/ALM) to increase the

differential. NOTE: The differential is adjustable from 1°C to 6°C.

• Once the required differential is selected, press the ‘set’ button to save the setting,

“E5.1” will be re-displayed.

• Wait 12 seconds,

The current temperature in the water heater will now be displayed and programming complete.


NOTES

• To adjust the differential setting for SE2 repeat the ‘Differential Adjustment’ steps above however when

selecting the ‘E’ parameter press the up button (▲/ALM) until “E5.2” is displayed.

• Do

NOT

adjust any other parameter settings; this may cause the thermostat to malfunction.