beautypg.com

Raypak B0109 User Manual

Page 20

background image

CONNECTIONS - PLUMBING

20

The table below provides indicative pipe and pump sizes for typical installations

Model Pump

Branch

Size

Minimum Manifold Header

Size Required (mm)

UPS

Series

Speed inches mm

1

Unit

2

Units

3

Units

4

Units

109

20-60B

3 1 25 25 32 32 40

147

20-60B

3 1

25 20 32 32 40


PUMP SELECTION

In order to obtain the best possible water flow in the system a correctly sized pump must be installed. Refer to the
Flow Rate and Pressure Drop table below and allow for the system head pressure when sizing the pump.

The pump selected should provide a 10 to 20°C

temperature difference between the water heater inlet and outlet

when the water heater is at full fire.

Mechanical heating systems with multiple zones may require additional pump(s) refer to ‘Multi Pump Options’ on
page 28.

WATER FLOW RATE AND PRESSURE DROP

10°C Rise

15°C Rise

20°C Rise

Model l/sec kPa l/sec kPa l/sec kPa

109 0.5 5.0 0.4 4.0 0.3 3.0

147 0.8 5.0 0.5 3.0 0.4 3.0


PRESSURE RELIEF VALVE

The pressure relief valve and elbow are shipped in a plastic bag inside the water heater.
The pressure relief valve must be fitted before the water heater is operated.

Fit the elbow supplied in the plastic bag to the connection on the inlet/outlet header then
screw the relief valve onto the other end of the elbow.

Seal the threads using Teflon tape, never hemp. A drain line must be
installed in accordance with AS/NZS 3500.4 to carry the discharge from
the valve to a suitable discharge point.

Relief Valve Pressure Rating

On/Off Models

850 kPa (125 psi)

Hi/Lo Models

310 kPa (45 psi)

When the water heater is connected to a storage cylinder for water heating applications, a correctly sized and
pressure rated TPR valve MUST be fitted to the storage cylinder.

NOTE:

Where a Hi/Lo water heater is used in a water heating application it will be necessary to replace the

310 kPa relief valve provided with the water heater with one rated at 850 kPa.

RELIEF VALVE DRAIN

A copper drain line must be fitted to the relief valve to carry the discharge clear of the water heater. Connect the
drain line to the relief valve using a disconnection union. The pipe work from the relief valve to the drain should be
as short as possible and fall all the way from the water heater with no restrictions. It should have no more than
three right angle bends in it. Use DN20 pipe.

The outlet of the drain line must be in such a position that flow out of the pipe can be easily seen (refer to
AS/NZS 3500.4) - but arranged so hot water discharge will not cause injury, damage or nuisance. The drain line
must discharge at an outlet or air break not more than 9 metres from the relief valve.

In locations where water pipes are prone to freezing, the drain line must be insulated and not exceed 300 mm in
length. In this instance, the drain line is to discharge into a tundish through an air gap of between 75 mm and
150 mm.

WARNING: The pressure relief valve on this water heater may discharge high temperature water under certain

conditions, it is strongly recommended the pipe work downstream of the relief valve be capable of carrying water
exceeding 93

°C. Failure to observe this precaution may result in damage to pipe work and property.

Pressure

Relief Valve

This manual is related to the following products: