Framing and Finishing

1)

Determine the total thickness of facing material (e.g. drywall plus
ceramic tiles) to allow the fi nished surface to be fl ush with the front
of the unit. Total facing thickness can vary from 1/2” (13mm) to 1-¼”
(32mm) thick.

2)

Frame in the enclosure for the unit with framing material.

3)

For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapor barrier and drywall, as per local
installation codes. (Do not insulate the fi replace itself.)

4)

The top of the unit must not be closer than 39” (990mm) to the
ceiling.

5)

Combustible material may be brought up to the top and
sides of the unit and be covered with ceramic tiles, bricks,
rock or other suitable combustible finishing materials.
Note: The unit does not have to be completely enclosed in a
chase. The clearance on top of the unit is 0” to the standoffs
so combustible building materials can be laid directly on top
of the standoffs. You must maintain proper clearances from
the vent to combustible materials (See Below).

6)

Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.

Drywall

Mantel Clearances

2

0

12

6

4

8

10

0

Side View

Top of

Louvers

12" (305mm)

3 ½" (89mm)

5 ½” (140mm)

A

Standoff

B

C

D

Header

Side Wall (Min 6”)

6”

3”

Mantel

leg

Mantel

leg

P48

Allowable mantel leg

projection.

3”

1-1/2"

Mantel Leg Clearances

Combustible mantel leg clearances as per diagram below:
Clearances are from the fi nished edge of the unit

Maximum
1-½” projection at 3”
minimum clearance.

Mantel Clearances

A

B

C

D

Front

41” (1041mm)

15” (381mm)

10” (254mm)

8” (203mm)

P48 Gas Fireplace

WARNING

Failure to maintain required clearances is a major cause of
chimney related fi res. Installation of this fi replace must comply
with these clearances.

Combustible Mantels

Because of the extreme heat this fi replace emits, the mantel
clearances are critical.
Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.

Note: If desired a non-combustible mantel may be installed at a

lower height.

Note: Ensure the paint that is used on the mantel and the facing

is “heat resistant” or the paint may discolour.

Clearance:

Dimension

Measured From:

A: Mantel Height

8” (203mm)

Minimum (Additional on this page)

B: Sidewall

6” (152mm)

Side of installed front

C: Ceiling

36” (914mm)

Top of installed unit

D: Mantel Depth

12” (305mm)

Maximum (Additional on this page)

E: Alcove Width

60” (1524mm)

Sidewall to Sidewall (Minimum)

F: Alcove Depth

36” (914mm)

Front to back wall (Maximum)

Top of Hearth must not be higher than the base of the fi rebox.

Vent Clearances

Clearance Dimension

Horizontal - Top

2-1/2” (64mm)

Horizontal - Side

1-1/2” (38mm)

Horizontal - Bottom

1-1/2” (38mm)

Vertical

1-1/4” (32mm)

E

B

B

A

C

D

F

Clearance Requirements

62

June 2007 Regency Product Specifi cations Book

Gas Fir

eplaces

Gas Fireplaces