• When equipped with two HI voltage power supplies, independent AC sources can be
used to power the product for greater redundancy.
2.2.2. DC Power Supply Wiring Examples
+
Figure 2.6. DC Single Power
Supply Wiring Example
+
+
Figure 2.7. DC Dual Redundant
Power Supply Wiring Example
• 88-300 VDC rated equipment: A 300 VDC appropriately rated circuit breaker must be
installed.
• A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
• For dual DC power supplies, Separate circuit breakers must be installed and separately
identified.
• Equipment must be installed according to the applicable country wiring codes.