2.2 POOL

HEATERS

A. General

1. The pool heater(s) shall be fired with gas at a rated input of

BTU/hr.

2. The pool heater(s) shall be CSA tested and certified with a minimum thermal efficiency of 85

percent at full fire.

3. The pool heater(s) shall be ASME inspected and HLW-stamped and National Board registered

for 160 PSIG working pressure, complete with a Manufacturer's Data Report.

4. The pool heater(s) shall have a floor loading of 65 lbs. /square foot or less.

B. Heat

Exchanger

1. The heat exchanger shall be of a single-bank, horizontal-grid design with eight integral Cupro

Nickel-finned tubes, each end of which is rolled into an ASME boiler-quality steel tube sheet.

2. The heat exchanger shall be sealed to 160 PSIG rated brass headers with high temperature

silicone "O" rings.

3. The low water volume heat exchanger shall be explosion-proof on the water side and shall

carry a twenty-year warranty against thermal shock.

4. The headers shall be secured to the tube sheet by stud bolts with flange nuts to permit

inspection and maintenance without removal of external piping connections. The heat
exchanger shall incorporate "V” baffles between the tubes to ensure complete contact of the
external tube surfaces with the products of combustion.

5. The pool heater(s) shall be capable of operating at inlet water temperatures as low as 105°F

without condensation.

6. The pool heater(s) shall be designed to accommodate field changes of either left or right hand

plumbing and electrical while leaving the tube bundle in place.

C. Burners

1. The tubular burners shall have multiport radial gas orifices, punched ports and slots, be

capable of quiet ignition and extinction without flashback at the orifice, and be manufactured
from corrosion-resistant titanium-stabilized stainless steel with low expansion coefficient.

2. The burners will be supplied with a fan-assisted, clean burning, and highly efficient fuel-air

mixture.

D. Ignition Control System

1. The pool heater(s) shall be equipped with a 100 percent safety shutdown system.
2. The ignition shall be Hot Surface Ignition type with full flame rectification by remote sensing

separate from the ignition source, with a three-try-for-ignition sequence, to ensure consistent
operation.

3. The igniter will be located away from the water inlet to protect the device from condensation

during startup.

4. The ignition control module shall include an LED that indicates six (6) individual diagnostic

flash codes.

5. Two external viewing ports shall be provided, permitting visual observation of burner

operation.

E. Gas

Train

1. The pool heater(s) shall have a firing/leak test valve and pressure test valve as required by

CSD-1.

2. The pool heater(s) shall have dual-seated main gas valve(s).
3. Gas control trains shall have a redundant safety shut-off feature, main gas regulator, shut-off

cock and plugged pressure tapping to meet the requirements of ANSI Z21.56/CSA 4.7.

F. Pool

Heater

Control

1. The following safety controls shall be provided:

a. High limit control
b. Flow switch, mounted and wired
c. 125 PSIG ASME pressure relief valve, piped by the installer to an approved drain
d. Temperature and pressure gauge
e. Poolstat