beautypg.com

Roberts Gorden Infrared Heater BH-150 User Manual

Page 14

background image

BH-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

8 of 59

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.

2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.

*When installed in the first 10' (3 m).

FIGURE 9: U-Tube, Opposite 45° Reflector

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

BH-40

- UNAPPROVED -

- UNAPPROVED -

BH-60

8

54

59

22

21

138

150

56

BH-80

8

60

65

22

21

153

166

56

BH-100

10

64

73

22

26

163

186

56

BH-115/125

10

70

77

22

26

178

196

56

BH-140/150

12

74

83

22

31

188

211

56

BH-175/200

12

76

85

22

31

194

216

56

B

A

C

D

FIGURE 10: 2-Foot Deco Grille and Protective Grille

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

BH-40

6

27

52

27

16

69

133

69

BH-60

6

35

62

35

16

89

158

89

BH-80

6

38

65

38

16

97

166

97

BH-100

6

40

70

40

16

102

178

102

BH-115/125

6

46

76

46

16

117

194

117

BH-140/150

6

50

79

50

16

127

201

127

BH-175/200

8

52

82

52

21

133

209

133

C

B

D

A

FIGURE 11: Lower Clearance Shield*

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

BH-40

6

34

27

34

16

87

69

87

BH-60

6

39

33

39

16

100

84

100

BH-80

6

40

38

40

16

102

97

102

BH-100

6

50

44

50

16

127

112

127

BH-115/125

6

54

48

54

16

138

122

138

BH-140/150

6

55

50

55

16

140

127

140

BH-175/200

- UNAPPROVED -

- UNAPPROVED -

C

B

D

A