Installation – Regency FREESTANDING WOODSTOVES F1100S User Manual

Page 11

background image

Regency Freestanding Woodstove

11

Minimum Alcove Clearance to Combustible Materials

The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.

Note: Minimum alcove ceiling height - 84"

Maximum depth of alcove - 36"

Minimum Overall Width (X) of Floor
Protector
for all installations:

Small Stove

F1100S

36"

Medium Stove

F2100M

36"

Medium Step Stove

S2100M

36"

Large Stove

F3100L

40"

Large Step Stove

S3100L

40"

Minimum Overall Depth (Y) of Floor Protector

Residential Residential Mobile Home Alcove

Unit "C" Vent Close Clearance Close Clearance

Y

Z

Y

Z

Y

Z

Y

Z

Small F1100S

with Airmate

38"

6"

37"*

5"

38"

6"

38"

6"

with Rear Deflector

38"

6"

37"*

5"

37"*

5"

37"*

5"

Medium F2100M

with Airmate

43"

6"

41.5"*

4.5"

43"

6"

41.5"*

4.5"

with Rear Deflector

43

6"

43"

6"

43"

6"

43"

6"

Medium S2100M Step Stove

43"

6"

41.5"*

4.5"

43"

6"

41.5"*

4.5"

Large F3100L

with Airmate

43"

6"

43"

6"

43"

6"

43"

6"

with Rear Deflector

43"

6"

43"

6"

43"

6"

n/a

n/a

Large S3100L Step Stove

43"

6"

43"

6"

43"

6"

43"

6"

INSTALLATION

From

From Flue

Min.

Min.Hearth

Unit

Unit

Center-line

Width

to Rear Wall

G

H

I

J

K

L

Small F1100S

with Airmate

11"

7"

23"

13.5"

46"

39"

with Rear Deflector

13"

5"

25"

11.5"

50"

37"

Medium F2100M

with Airmate

10"

4.5"

22"

11.5"

44"

41.5"

with Rear Deflector

14"

7"

26.5"

14"

52"

44"

Medium S2100M Step Stove

10"

4.5"

22"

11.5"

44"

41.5"

Large F3100L

with Airmate

16"

9.5"

30"

16"

60"

46.5"

with Rear Deflector (not approved for Alcove)

Large S3100L Step Stove

16"

9.5"

30"

16"

60"

46.5"

*The rear clearance to combustibles is less than 6", for corner installations the rear corners may be angled to take advantage of the closer clearances.

Floor Protection

A combustible floor must be protected by a non-combustible material (like tile,
concrete board, or certified to UL-1618 or as defined by local codes) extending
beneath the heater and a minimum of 6" from each side and minimum 16" from
the front face of the stove and minimum 6" (or the rear clearance to
combustibles whichever is smaller) from the rear of the stove.

NOTE: In Canada, floor protection must extend 18" to the front and 8" to each side of the stove.