beautypg.com

Installation, Aeration adjustment, Log set installation – Regency U37-LP PROPANE User Manual

Page 17: Gas connection, High elevation

background image

U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater

17

INSTALLATION

AERATION

ADJUSTMENT

The burner aeration is factory set but may need
adjusting due to either the local gas supply, air
supply or altitude.

Natural Gas:

1/4" open

Propane:

3/8" open

The aeration adjustment gears are located on
the right side of the burner box and can be
accessed from the side or from the front when
the louvers are removed.

To adjust the aeration: use the allen key to turn
the turning gear which will adjust the air shut-
ter. Open the air shutter for a blue flame or close
it for a yellower flame. The factory setting
should be sufficient for most installations.

Clockwise to open,

counter-clockwise to close.

Caution: Carbon will be produced if the air
shutter is closed too much.

Note: Any damage due to carboning re-

sulting from improperly setting
the aeration controls is NOT cov-
ered under warranty.

Note: Aeration Adjustment should only

be performed by an authorized
Regency Installer at the time of
installation or service.

LOG SET

INSTALLATION

Read the instructions below carefully
and refer to the diagrams. If logs are
broken do not use the unit until they are
replaced. Broken logs can interfere with
the pilot operation.

The gas log kit contains the following:

a) 02-65

Rear Log

902-267

b) 02-56

Middle Left Log

902-230

c) 02-44

Front Left Log

902-228

d) 02-46

Left Top Log

902-231

e ) 02-45

Front Right Log

902-229

f)

02-47

Center Log

902-232

g) 02-48

Middle Right Log

902-226

h)

Embers

902-151

i)

Lava

902-154

Embers.

Embers

The "02" refer numbers (i.e. 02-65) are

molded into the rear of each log.

1) Carefully remove the logs from the box and

unwrap them. The logs are fragile, handle
with care - do not force into position.

2) Sprinkle the embers on the left and right

sides of the firebox base.

GAS CONNECTION

The gas connection is a 3/8" NPT 90

o

elbow.

The gas line can be rigid pipe or to make
installation easier, use a listed flexible connec-
tor and/or copper tubing if allowed by local
codes. Since some municipalities have addi-
tional local codes it is always best to consult
with your local authorities and the CAN/CGA
B149 installation codes. For USA installations
follow local codes and/or the current National
Fuel Gas Code, ANSI Z223.1.

When using copper or flex connectors use
only approved fittings. Always provide a union
so that gas lines can be easily disconnected for
burner and/or valve servicing. Flare nuts for
copper lines and flex connectors are usually
considered to meet this requirement.

Important: Always check for gas leaks
with a soap and water solution or gas
leak detector. Do not use open flame for
leak testing.

Note: Prior to any pressure testing of

the gas supply piping system that
exceeds test pressures of 1/2
psig, this appliance must be dis-
connected from the piping sys-
tem. If test pressures equal to or
less than 1/2 psig are used then
this appliance must be isolated
from the piping system by clos-
ing its individual manual shut-off
valve during the testing.

HIGH ELEVATION

This unit is approved in Canada for altitude 0 ft. to
4500 ft. (CAN/CGA-2.17-M91). For Natural Gas
installations above 4500 ft. follow current CAN/
CGA-B149.1.

System Data - U37

For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:

Natural Gas Propane
Burner

#37

#52

Max. Input Rating

30,000 Btu/h

Min. Input Rating

15,000 Btu/h

Supply Pressure

Natural Gas

min. 5.0" w.c.

Propane

min. 12.0" w.c.

Manifold Pressure

Natural Gas

3.8" +/- 0.2" w.c.

Propane

11" +/- 0.2" w.c.