Remote direct communications – Rackmount Solutions XRT Series User Manual
Page 39

38
REMOTE DIRECT COMMUNICATIONS
Pin 1:
Not Used
Pin 2:
LBW
Output signal from UPS (RS232 levels)
High signal (+3 to +12 volts)= Low
Battery Warning
Pin 3: UPS Shutdown
Input signal to UPS, Shuts down
UPS (RS232 levels)
High signal (+3 to +12 volts) = UPS OFF
Pin 4: AC Fail NO.
Output signal from UPS, open
collector, High impedance = AC OK
Low impedance to ground = AC Failed
Pin 5: Ground
Common Return
Pin 6: Low Battery Warning
Output signal from UPS, open
collector
High impedance = OK
Low impedance to ground = Low
Battery Warning
Pin 7: AC Fail NC
Output signal from UPS, open
collector High impedance = AC Failed
Low impedance to ground = AC OK
Pin 8: AC Fail Logic Signal
Output signal from UPS, logic level
Logic High (+3 to +12 volts) =
AC failed
Logic Low (0 volts) = AC OK
Pin 9: Remote Shutdown
Input signal to UPS, pulled to 5
VDC through 10 K ohms
>2.4 VDC = Normal output
<0.8 VDC = Output off