Freedom F-64 Installation Instructions

WI1501A 9/06

Page 7

Smoke Detectors, 4-Wire:

1. ESL 445AT, 445C, 445CT, 445CR, 445CRT
2. Hochiki America SLG-12 with YBC-RL4-RA Base
3. System Sensor 2312/24T; 1412; 1412TH; 2412TH
Subtract total smoke-detector alarm current from available standby current.
Note: Any normally-open devices that do not require power from the control panel, such as pull stations and

thermostats may be used if acceptable to the Authority having Jurisdiction.

UL Compatible Smoke Detectors (Providing UL Recognition or Listing)

Manufacturer

4-Wire

Smoke Detector

2-Wire

Smoke Detector *

Smoke Detector

Base

Napco

FW-4

FW-2

Sentrol






System

Sensor



449AT
449C
449CRT
449CST
449CSRT
449CSRH
449CSST

449CLT
449CSLT
449CTE
741U
742U

712U
722U
732U
711U
721U
721UT

731U

1112
2112

2112T
2112TSRB

2100
2100T

1100

701U
702U
702RE
702RU

Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10

SUMMARY OF UL REQUIREMENTS

Residential

Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.

FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors)

Minimum alarm timeout of 5 minutes

Maximum exit time: 60 seconds

Maximum entry time: 45 seconds

Do not program “Swinger Shutdown”, “Auto-Bypass” or “50 ms Loop Response”

“Abort Delay” may not exceed 45 seconds

Program “Disable Callback Download”

Automatic dialer may not dial a police station number that has not been dedicated for such service

System must be tested at least weekly under AC/battery and Battery-Only conditions

Replace the rechargeable battery at least every 5 years

If the battery is heavily discharged, replace it or have it tested by a qualified technician

For silent panic, connect only to UL-listed holdup devices

All zones must be programmed for “Priority”

Do not program any zones for “Keyswitch Arming”

System must be serviced at least once every year

Residential Fire and Combination Residential Fire & Burglary must program “Residential Fire”

Touchpad / Keypad Expansion (EZM) Zones are not to be used as fire zones

Touchpad / Keypad Auxiliary is not to be selected

The Freedom F-64 series Touchpads must have labels placed on only the appropriate Touchpad keys (Fire, Police and
Auxiliary) that are operational

Install in accordance with the NEC/CEC requirements

"Force Arm" and "Selective Bypass" must not be programmed for UL installations

UL Compatible Sounding Appliance:

Wheelock AH-12WP

Smok

e Dete

cto
rs & Su

mmar

y of UL Re

quirements