Napco Security Technologies WI1501A User Manual
Page 26

Freedom F-64 Installation Instructions
L
NAPCO Security Systems
WI1501A 9/06
Page 26
display and pulsing sounder. An open circuit on the Fire Zone will identify a trouble and cause flashing "
SYSTEM TROUBLE/E41-00
SERVICE
" LCD display and pulsing sounder after a 10-second delay. The sounder may be silenced by pressing RESET. The LED will
go off within 30 seconds after reset if the alarm or trouble is cleared. For Smoke-Detector Reset, see Alarm Outputs. 
Fire or Keypad Fire can be made to trip an alarm or report to Central Station. If Keypad Fire is programmed, pressing both the 
7
and
G
buttons at the keypad at the same time (hold down the
I
button for 2 seconds at the Touchpad) will sound a fire panic alarm
and display "
FIRE ALARM
" at the keypad. The Keypad Fire function is supplementary to the hardwired zones. Note: This feature shall
not be considered a substitute for listed manual initiating devices. A fire condition that has not been restored will cause the zone number 
and description to scroll. To reset (acknowledge) the condition, enter a valid code, then press the 
U
button.
 
Fire Verification (Not for use in California) 
An alarm on any Fire Zone programmed for "Fire Verification" and connected to the fire power terminal will cause all fire zones to be 
powered down for 12 seconds. (All devices must be wired with + power on Terminal 25). After this time, power is restored and a 4-
second power-up time is started. Thereafter, the zone will be active again. This represents a total processing delay of 16 seconds from 
the time the alarm is first detected. If an alarm condition still exists at this time or reoccurs within 2 minutes, an alarm will be initiated, 
otherwise the zone will return to its original state. Note: A zone programmed for "Fire Verification" must be programmed as a "Fire 
Zone" as well. 
 
GEM-Print 
A printer can be made to print all logged operations directly from the panel, when programmed for "Enable GEM-PRINT Module" and a 
separate Gem-Print Module is added to the panel. 
 
Include Selective Bypass In Conditional Closing/Status See Closing Report. 
 
Inhibit System Trouble Audible at Keypad/Touchpad  (Do not program in UL installations) 
For installations where an audible during a system trouble is not desired, an option, Inhibit System Trouble Audible can be enabled. 
Regardless of the system status (Armed or Disarmed) there is no Touchpad/keypad sounder in the event of a system trouble. However, 
the trouble will still scroll in the Touchpad/keypad display until RESET is pressed and the SYS TBL icon will display until the trouble is 
restored. 
•
To disable System Trouble Audible, enable the option Disable System Trouble Audible in the PCD-Windows Keypad Features 
screen. 
 
Interior Stay Zones; Interior Normally Bypassed (Stay Mode); Auto Interior Bypass (Stay)/Easy Exit 
Must be programmed. See Operating Instructions for arming details. 
 
Interior (STAY) Bypass 
Interior Zones, when bypassed, allow free movement within the home while the protection of armed perimeter zones is maintained. To 
bypass Interior Zones, press 
P
. All zones (including Interior Bypass Zones) are all protected with full protection, in ARMED AWAY
mode. 
 
Jumpers (Refer to Wiring Diagram for UL configuration) 
JP1: This control panel jumper (located at the top center of the panel) is installed across top and center pins for normal operation.
When configuring a Freedom Touchpad, move jumper across center and lower pins.
JP3: 2-Wire Fire jumpers. Select Zones 7 and/or 8 for use as either 2-Wire Fire Zones or Burglary Zones.
 
Keyfob Control of Relay Groups 1 and 2 
The F-64 supports Keyfob Control of Relay groups 1 and 2. The Keyfob Aux 1 and Aux 2 buttons can be programmed to toggle on and 
off external Relay Groups 1 and 2. 
 
Keyfob Arm/Disarm chirp of Alarm Output. 
The Keyfob Arm/Disarm chirp can be directed to the Alarm Output, which can free up the PGM2 Output for other uses such as garage 
door opener control. To enable the Keyfob Arm/Disarm chirp option on Alarm Output, enable "Chirp Output on Keyfob Arm/Disarm" and 
"Select Alarm Output for Keyfob Chirp" in the PCD-Windows Options screen or in Direct Address Program Mode. 
 
Keyfob Transmitters; Chirp Output on Keyfob; Select Alarm for Keyfob Chirp 
Keyfob transmitters can (1) operate up to four zones, or (2) can Arm/Disarm an area and provide two Auxiliary control buttons, but 
cannot be operated in these two modes simultaneously. A Keyfob Transmitter set up to Arm/Disarm an area with "PGM2 Chirp on 
Keyfob Arm/Disarm" will cause a 1 chirp sound on arming and a 2 chirp sound on disarming, by using an steady state Alarm Output (not 
a Pulse Alarm, Cadence Pulse Alarm or Voice Siren Driver). Programming the Auxiliary Keyfob Buttons to "C: PGM2 Output Toggle" on 
Auxiliary 1 or 2 buttons will cause PGM2 to toggle the current condition of the PGM2 output. Keyfob 1-8 can have their opening / 
closings reported as users 57 through 64, respectively. 
Glo
ssar
y
