background image

Chapter 2

Configuration and Installation

© National Instruments Corporation

2-17

PC-DIO-96 User Manual

Mode 2 Bidirectional Timing

The following figure illustrates the timing specifications for bidirectional transfers in mode 2.

T2

T1

WR*

OBF*

INTR

ACK*

DATA

T6

T7

T3

T4

T10

STB*

T9

T8

T5

IBF

RD*

Name

Description

Minimum

Maximum

T1

WR* = 1 to OBF* = 0

150

T2

Data before STB* = 1

20

T3

STB* pulse width

100

T4

STB* = 0 to IBF = 1

150

T5

Data after STB* = 1

50

T6

ACK* = 0 to OBF = 1

150

T7

ACK* pulse width

100

T8

ACK* = 0 to output

150

T9

ACK* = 1 to output float

20

250

T10

RD* = 1 to IBF = 0

150

All timing values are in nanoseconds.