beautypg.com

Nordyne Downflow Direct Vent Forced Air Gas Oil Furnaces SERIES M1B User Manual

Page 26

background image

26

TROUBLESHOOTING

Standing Pilot Models
Main Burner Does Not Ignite
1. Check the electrical supply to the furnace.
2. Verify the furnace furnace On-Off switch is in

the ON position.

3. Check for proper thermostat operation.
4. Check for broken or open thermostat wires.
5. Verify the insulation located on the inside of

the front panel is glued securely around the
fan switch and the limit switch.

6. Shut off the electrical supply to the furnace

and remove the electrical box cover.

7. Check for a defective transformer or blown

fuse.

8. Check electrical circuit for proper grounding,

polarity, and make sure the electrical
connections are tight.

9. Check the limit switches. Did they fail to close?
10. Replace the electrical box cover and restore

electrical power to the furnace. Turn the
furnace On-Off switch to ON and raise the
thermostat setting above room temperature.

11. Check for 24 VAC at the gas valve. Replace

the valve if the pilot is established and it
does not open when powered with 24 volts.

Powered (24 VAC) Gas Valve - No Main Flame
1. Verify the manual shut-off valve is OFF.
2. Check the pilot fl ame. It must be established.
3. Check the gas valve control lever. It must be

in the ON position.

4. Check incoming gas pressure.
5. Replace the gas valve if the main burner does

not come on under the above conditions.

Pilot Will Not Light or Goes Out
1. Check the incoming gas pressure.
2. Check for the proper pilot orifice. See

specifi cations on the furnace nameplate.

3. Check for proper pilot fl ame adjustment. See

Burner Adjustment section (page 22).

4. Verify the thermocouple millivoltage. If reading

is not between 18 - 30 mv., the gas valve
electromagnet may be defective. Replace the
gas valve if necessary.

5. Verify the pilot shield is in place.
6. Check for gas leaks (page 18).
7. Check the fl ue assembly for air leaks.
8. See lighting procedures (pages 20 - 22).

Main Flame Is Not Burning Properly
1. Check the manifold gas pressure.
2. Check for the correct main burner orifi ce. See

furnace nameplate for specifi cations.

3. Check the fl ue for any blockages or loose

connections.

4. Check the combustion air passages for

blockage.

High Gas Bills
a. Verify the proper orifi ces are being used.
b. Check the return air system. Is it clear and

free of blockage?

c. Check the furnace fi lter. Is it clean or need

replacing?

d. Verify the home is insulated, windows and

doors fi t tightly, and there are no leaks in the
heating duct system.

e. Check the room thermostat. Is the setting

higher than necessary? Low humidity requires
higher temperatures for the same level of
comfort. Check for proper humidity level in the
home.

Direct Ignition Furnaces Including Gas Gun
M1B Series (see Table 9, page 29)

Burner Motor won’t Run - T-stat Calls for Heat
1. Check the electrical supply to the furnace.
2. Verify the furnace furnace On-Off switch is in

the ON position.

3. Defective thermostat circuit - white and red

thermostat low voltage leads (M1/M5M,
M1/M5B models). If the burner motor or
combustion fan runs, check:

• Thermostat connections
• Thermostat

4. No voltage to control module - determine if 24

volts (or 120 volts) is available to the control
module. If voltage is not available check for:

• Blown fuse, defective transformer, circuit

breaker, no electrical supply.

• Limit switch open.
• Loose connections.

Combustion Blower Runs - No Flame
1. Defective centrifugal switch (M1B Model).

• Check the operation of centrifugal switch

by removing end bell of the burner motor.

• Clean contacts of motor.
• If the contacts are closed, replace the motor.

2. Defective pressure switch (M1M & M1G - 077,

090 Models) - check air tube and electrical
connections.

3. Burner in purge mode - allow 75 seconds for

fl ame establishing period.

4. Check for proper electrical connections at

purge timer, control box, or gas valve.

5. Check for gas supply - gas line valve on, control

lever on.

Control Module is Powered - Ignitor won’t Heat
Up
1. Disconnect ignitor leads at AMP receptacle and

check for 120 volts at the plug during ignition
sequence.

2. Replace ignition control if 120 volts is not

available at AMP plug during ignition sequence.