beautypg.com

Warning – Nordyne Downflow Direct Vent Forced Air Gas Oil Furnaces SERIES M1B User Manual

Page 19

background image

19

Figure 28. Honeywell Gas Valve

PRESSURE

REGULATOR

CAP

M11678

N

A

T N

A

T

L

P

L

P

N

A

T N

A

T

OR

OTHER SIDE

OF CAP

LP Gas

Configuration

Black Cover

Red

Natural Gas

Configuration

Figure 29. Robertshaw Gas Valve

High Altitude Conversion
High altitude conversion with this furnace
depends on the installation altitude and the
heating value of the gas. The installation of this
furnace at altitudes above 2,000 feet must meet
the requirements of the National Fuel Gas Code
or local jurisdiction. In Canada, the requirements
for high altitude are different and governed by
CGA B149.1. Please consult your local code
authority.

WARNING:

The reduction of input rating nec-
essary for high altitude installation
may only be accomplished with
factory supplied orifi ces. Do not
attempt to drill out orifi ces in the
fi eld. Improperly drilled orifi ces
may cause fi re, explosion, carbon
monoxide poisoning, personal
injury or death.

This furnace is shipped from the factory with
orifi ces and gas regulator settings for natural gas
operation at sea level altitudes. At 2000 feet, the
NFGC requires that this appliance be derated
4% for each 1000 feet of altitude. For example,
the input needs to be reduced 8% at 2,000 feet,
12% at 3,000 feet and etc. This deration is in
reference to the input rate and gas heating value
at sea level. See Table 12 (page 32).

6. For Honeywell gas valves with the regulator

converter (Figure 28, page 19):

a. Unscrew the pressure regulator cap and

check for the letters NAT or LP.

b. Invert the cap and tighten until snug.

7. For Robertshaw gas valves with the regulator

converter (Figure 29):

a. Remove the black cover and unscrew the

converter located on top of the gas valve.

b. Invert the converter: for LP the red ring will

be located at the bottom and the LP stamping
on the converter will appear right side up.

c. Screw converter back into the regulator,

hand tight plus 1/8 turn. Replace the black
cover on the converter top to protect the
threads.

8. Reassemble the burner assembly into the

furnace.

9. Reconnect the gas piping and electrical wires

to the gas valve.

10. Open the manual shut-off valve and follow

the Lighting and Operating instructions on
page 22.

Flue Gas Sampling
It may be necessary to take fl ue gas sampling
from oil and gas furnaces (M5S and M1B Series
Models) in order to check the performance after
furnace installation. A fl ue gas sample may
be taken from the heat exchanger, which is
located behind the hole of the top-front of blower
compartment.

1. Turn off all electric power to the appliance.
2. Remove the black plastic cap located above

the blower. Do not discard cap.

3. Drill a hole through the top of the blower

compartment. NOTE: Hole diameter should
be same size as sampling tube.

4. Insert sampling tube through the drilled hole

and into the heat exchanger.

5. After a complete check and adjustment

of furnace performance, seal the drilled
hole with a screw larger than the hole.
NOTE: Seal the screw threads with silicon
sealant - rated at least 500° F.

6. Plug the outside hole with the plastic cap

removed in step 3.