beautypg.com

Figure #7 remote mounted blower packs (rmbp), Figure #6 remote mounted blower pack – Nortec NHDI User Manual

Page 6

background image

and visible from within the plumbing section of
the unit, and that the unit’s flanges are
properly contained within the wall bracket.

5.

Install tank bracket. See Figure #5. (NHSC
Version only). Mounting the scale tank. (NHSC
Version only).

6.

Make sure humidifier is level.

7.

DO NOT mount humidifier on hot surfaces.

8.

If humidifiers are mounted on roof, a
thermostatically ventilated weatherproof

cabinet provided by others should be used.
Consult factory.

9.

DO NOT mount humidifiers on vibrating
surfaces or duct work.

BLOWER PACKS

1.

Blower packs are an optional accessory used
to directly distribute steam to localized areas
(such as computer rooms) or in structures that
do not have a built-in air distribution system.

- 3 -

23.0"

(58.4 cm)

11.0"

(28.0 cm)

2.9"

(7.3 cm)

14.2"

(36.2 cm)

7.2"

(18.2 cm)

7.7"

(19.5 cm)

Power

Steam

Condensate

Dimensions Shown
Are Steam Line Connections
Allow Minimum 12" (31 cm)
Clearance On Each Side

Wall

Mounting

Bracket

Figure #7

Remote Mounted Blower Packs (RMBP)

Scale
Collector
Tank

Remote

Mounted

Blower Pack

Figure #6

Remote Mounted Blower Pack

Remote Mounted Blower

Packs (RMBP) Only

NHSC

NHDI

uses Nortec steam

hose 1.75" O.D.or
stainless steel pipe.

uses Nortec steam

hose 1.75” O.D. or
stainless steel pipe.

Do not exceed 10 ft
when using steam hose.

Low Voltage

Controls Wiring

24 Vac
Primary Wiring

Copper Funnel

Drain (by others)

Air

Gap

Scale

Collector

Tank - NHSC

Humidistat

Steam Line
Connection

LCD Keypad

Display with

LED Status

NHSC / NHDI using a Remote Mounted Blower Pack (RMBP)

3"

Min. Trap
Height 3"
Required

Water

Supply 3/8”

Drain Line

1.75” O.D.

Figure #8

Typical Remote Mounted Blower Pack Installation

This manual is related to the following products: