LOCATION & MOUNTING
HUMIDIFIERS
NHSC / NHDI Series humidifiers are designed to
mount on a suitable wall or vertical surface. Do not sit
the unit on floor due to clearances required for
plumbing, electrical, and control entrances. The
clearance dimensions shown in this manual are for
reference only and are the minimum required for
maintenance of the humidifier. Local and National
Codes should be consulted prior to final location and
installation of the humidifier. NORTEC will not accept
responsibility for installation code violations.
1.
Location of the humidifier should be below and
as close as possible to the steam distributor
location. If possible, DO NOT locate humidifier
any further than absolutely necessary from
steam distributor location, as controllability
and net output will be reduced as a result of
heat loss through the steam hose (see Steam
Distribution Engineering Manual).
2.
Where possible, mount humidifier at a height
convenient for servicing.
3.
Wall mounting bracket provided should be
securely attached horizontally and open edge
facing upwards, using field-supplied fasteners.
For a single unit, use a minimum of 4 - #12 x
3” long wood screws. For a double unit, use a
minimum of 6 - #12 x 3” long wood screws.
These screws must be fastened securely on a
2 x 4 wood stud or equivalent support. If any
spacer material is used between the bracket
and the structural material such as drywall,
increase fastener length accordingly. In
addition, install a minimum of 2 field supplied
fasteners in the holes provided in the back of
the unit to prevent the unit from being bumped
off the wall bracket. See Figure #4.
4.
Mount unit on hanging bracket after ensuring
the bracket is properly anchored to the wall.
Raise the unit and place it on the hanging
bracket ensuring that the flanges in the
mounting bracket are properly aligned and
centered with the flanges of the unit. Push the
unit in towards the wall to properly interlock
the two flanges. Note: This will result in the
unit shifting slightly down. Ensure that the
hanging bracket’s flanges are fully engaged
- 2 -
Frontal clearance min. 36" (91 cm)
Right side clearance min. 36" (91 cm)
Left side clearance min. 2" (5 cm)
Wall
7.7"
(19.6 cm)
Figure #4
Wall Bracket Mounting
1) Line up holes in bracket with
holes in drain pan. Fasten the
bracket to the drain pan using
the four Nylon lock nuts
provided.
2) Fasten the front of bracket
with the two #10-24 self tapping
screws provided.
3) The two locking screws for the
bracket should already be
installed.
1.
2.
3.
1.
Figure #5
Installation of the Scale Tank Bracket (NHSC only)
NOTE: Local and national codes may deviate, please
consult applicable codes for clearance requirements.
Right side min. 36" side clearance. Min. 36" frontal
clearance recommended see note.
Top 12” Min, Bottom 12” Min, and Left Side 2” Min.
Condensate Return
Steam Outlet
Right Side
Front
Figure #3
Clearance Required (Top View)