Maintenance – Nortec NHDI User Manual

Page 20

background image

Unit Type

Warning: In order to eliminate faults, the steam

humidifier must be switched off and secured against
unintentional re-connection. Take care that the
electricity supply to the main contactor is disconnected
(check with voltage meter).

Only allow trained and qualified personnel to

repair faults. Faults relating to electrical installation
(e.g. change of unit fuse) must only be carried out by
authorized personnel.

Repair work and replacement of faulty

components must only be carried out by your service
technician!

MAINTENANCE

All maintenance work must be performed by

adequately qualified and trained personnel familiar
with the dangers involved. Ascertaining the
qualifications is the customer’s responsibility.

Instructions and details concerning the

maintenance work must be observed and adhered to
without fail.

Only the type of maintenance work outlined in this

documentation must be carried out.

Use original spare parts exclusively to replace

defective parts.

Before maintenance is initiated, the steam

humidifier must be taken out of operation in
accordance with instructions in the manual and
protected against unintentionally switching on the
humidifier.

NOTES ON MAINTENANCE

To safeguard reliable operation, the maintenance

of the NHSC should be devised in three stages. A
distinction is made here between periodic inspections,
minor servicing and major maintenance of the
steam-air humidifier.

The intervals required between minor servicing

and major maintenance depend on the water quality
and the quality of steam generated and can be
pre-selected on the rotary switch “S2” on the control
board. After expiry of the selected interval, the yellow
LED flashed and an appropriate message alternates
with the normal operation indication.

The following is an overview of the work that

should be undertaken for the three maintenance
stages.

Periodic Inspections

When

Once per week

Work

Inspect the water and steam
installations for correct sealing and any
possible damage.

Inspect the drain line for soiling.

Inspect the electrical installation for
loose cables and damaged
components.

Inspect the humidifier for irregularities
both external and internal.

- 17 -

Figure #20

Minor Servicing - NHSC ONLY

- Unit indicates cleaning is
required.

- This cleaning normally occurs
once a year(depends on water
quality).

- The scale collector tank and the
stainless steel tank are removed
and cleaned.

- Check all plumbing and
electrical components for any
issues.

NHSC Maintenance

Complete cleaning

(between 600 - 6000

hours of operation)

Figure #21

Major Maintenance - NHSC / NHDI

machine type

xxlb/xxxV