10.0 Installation

© Baxi Heating UK Ltd 2008

10.7

Fitting The Flue

HORIZONTAL FLUE

1. The standard flue is suitable for lengths between 100mm

minimum and 685mm maximum, as measured from the

edge of the flue elbow outlet to the joint between the

terminal and air duct (Fig. 48).

2. Locate the flue elbow on the adaptor at the top of the

boiler. Set the elbow to the required orientation (Fig. 50).

The elbow is fully engaged when there is a distance of

20mm from the adaptor to the indicator line (Fig. 49).

NOTE: The flue elbow is angled at 93 degrees to

ensure a fall back to the boiler.

3. Measure the distance from the outside wall face to the

elbow. This dimension will be known as ‘X’ (Fig. 51).

4. To dimension ‘X’ add 50mm. This dimension to be

known as ‘Y’.

IMPORTANT: Check all dimensions before cutting.

5. Mark dimension ‘Y’ on the flue as shown (Fig. 52).

Carefully cut the waste material from the flue, ensuring that

the ducts are square and free from burrs.

Fig. 52

Wall Thickness

(X)

Wall Thickness

(X)

Flue Elbow

Fig. 48

Fig. 50

Adaptor

Apply Lubricant for
ease of assembly.

Ensure Elbow is fully

engaged into Boiler

Adaptor

20mm

Indicator line

Fig. 51

100mm

685mm

Y

Flue

Waste

Fig. 49