EXTENSION CORDS

Use proper extension cords. Make sure your extension cord is in good condition and is a 3-wire

extension cord which has a 3-prong grounding type plug and matching receptacle which will accept the machine’s
plug. When using an extension cord, be sure to use one heavy enough to carry the current of the machine. An
undersized cord will cause a drop in line voltage, resulting in loss of power and overheating. Fig. D-1 or D-2, shows
the correct gauge to use depending on the cord length. If in doubt, use the next heavier gauge. The smaller the gauge
number, the heavier the cord.

Fig. D-1

Fig. D-2

MINIMUM GAUGE EXTENSION CORD

RECOMMENDED SIZES FOR USE WITH STATIONARY ELECTRIC MACHINES

Ampere

Total Length

Gauge of

Rating

Volts

of Cord in Feet

Extension Cord

0-6

120

up to 25

18 AWG

0-6

120

25-50

16 AWG

0-6

120

50-100

16 AWG

0-6

120

100-150

14 AWG

6-10

120

up to 25

18 AWG

6-10

120

25-50

16 AWG

6-10

120

50-100

14 AWG

6-10

120

100-150

12 AWG

10-12

120

up to 25

16 AWG

10-12

120

25-50

16 AWG

10-12

120

50-100

14 AWG

10-12

120

100-150

12 AWG

12-16

120

up to 25

14 AWG

12-16

120

25-50

12 AWG

12-16

120

GREATER THAN 50 FEET NOT RECOMMENDED

MINIMUM GAUGE EXTENSION CORD

RECOMMENDED SIZES FOR USE WITH STATIONARY ELECTRIC MACHINES

Ampere

Total Length

Gauge of

Rating

Volts

of Cord in Feet

Extension Cord

0-6

240

up to 50

18 AWG

0-6

240

50-100

16 AWG

0-6

240

100-200

16 AWG

0-6

240

200-300

14 AWG

6-10

240

up to 50

18 AWG

6-10

240

50-100

16 AWG

6-10

240

100-200

14 AWG

6-10

240

200-300

12 AWG

10-12

240

up to 50

16 AWG

10-12

240

50-100

16 AWG

10-12

240

100-200

14 AWG

10-12

240

200-300

12 AWG

12-16

240

up to 50

14 AWG

12-16

240

50-100

12 AWG

12-16

240

GREATER THAN 100 FEET NOT RECOMMENDED

3. 240 VOLT SINGLE PHASE OPERATION
The motor supplied with your saw is a dual voltage,
120/240 volt motor. It is set at the factory at 120 volts. If
it is desired to operate your machine at 240 volts, single
phase, it is necessary to reconnect the motor leads in
the motor junction box by following instructions given on
the motor nameplate or inside the junction box.

MAKE SURE MOTOR IS

DISCONNECTED FROM POWER SOURCE BEFORE
RECONNECTING MOTOR LEADS.

It is also necessary to replace the 120 volt plug, supplied
with the motor, with a UL/CSA listed plug suitable for
240 volts and the rated current of your machine as
illustrated in Fig. C. Contact your local Authorized Delta
Service Center or qualified electrician for proper
procedures to install the plug. The machine must comply
with all local and national electrical codes after the 240
volt plug is installed.
The machine with a 240 volt plug should only be
connected to an outlet having the same configuration as
the plug illustrated in Fig. C. No adapter is available or
should be used with the 240 Volt plug.

IN ALL CASES, MAKE CERTAIN THE

RECEPTACLE IN QUESTION IS PROPERLY GROUNDED. IF
YOU ARE NOT SURE HAVE A QUALIFIED ELECTRICIAN
CHECK THE RECEPTACLE.

Fig. C

GROUNDED OUTLET BOX

CURRENT

CARRYING

PRONGS

GROUNDING BLADE
IS LONGEST OF THE 3 BLADES

4. Permanently connected machines:
If the machine is intended to be permanently connected, all
wiring must be done by a qualified electrician and conform
to the National Electric Code and all local codes and
ordinances.

* THREE PHASE OPERATION: Three phase machines
are not supplied with a power cord and must be
permanently connected to a building’s electrical
system. Extension cords can’t be used with a three
phase machine.
* LVC MAGNETIC MOTOR CONTROL: If you purch-
ased a machine that has a Low Voltage Magnetic Motor
Control System, refer to its instruction manual for
installation guidance.