Balance refrigerant of the 2-way, 3-way valves – Panasonic CU-C12DKU User Manual

Page 49

background image

(Lack of refrigerant in the refrigeration cycle)

Procedure:
1. Confirm that both the 2-way and 3-way valves are set to

the open position.

2. Connect the charge set to the 3-way valve’s service

port.

Leave the valve on the charge set closed.

Connect the charge hose with the push-pin to the
service port.

3. Connect the charge set’s centre hose to refrigerant

reclaiming equipment.

Purge the air from charge hose.

4. Open the valve (Low side) on the charge set and

discharge the refrigerant until the gauge indicates 7.25
PSI (0.5 kg/cm

2

G) to 14.5 PSI (1 kg/cm

2

G).

If there is no air in the refrigeration cycle (the pressure
when the air conditioner is not running is higher than 0.1
PSI (1 kg/cm

2

G), discharge the refrigerant until the

gauge indicates 7.25 PSI (0.5 km/cm

2

G) to 14.5 PSI (1

kg/cm

2

G). If this is the case, it will not be necessary to

apply a evacuation.

Discharge the refrigerant gradually; if it is discharged
too suddenly, the refrigeration oil will also be
discharged.

5. Turn on refrigerant reclaiming equipment.

11.4. Balance refrigerant of the 2-way, 3-way valves

49

CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU