beautypg.com

Polycom DOC2559A User Manual

Page 20

background image

Chapter 1- Hardware Description

1-14

3

Fasten the RMX to the rack with 8 screws into the holes provided on

the RMX’s front as shown in Figure 1-3.

Figure 1-3

RMX 4000 Rack Mount

The airflow of the RMX 4000 is from right to left. Be sure that the

areas on the left and right side of the system are clear for proper
ventilation.

Rack mounting screws must be supplied by the rack’s manufacturer.

When the unit is installed on a rack, the rack must be properly grounded to the
central office ground. The rack must be grounded with two-hole compression-
type connectors using copper conductors (tinned or untinned). Wire, bus bar or
braided strap connectors are acceptable.