beautypg.com

Maintenance, Caution, Danger – PB Heat Gas Boiler User Manual

Page 37

background image

35

A. GENERAL (WITH BOILER IN USE)

General boiler observation can be performed by the
owner. If any potential problems are found, a qualified
installer or service technician/agency must be notified.

1. Remove any combustible materials, gasoline and

other flammable liquids and substances that generate
flammable vapors from the area where the boiler is
contained.

2. Observe general boiler conditions (unusual noises,

vibrations, etc.)

3. Observe operating temperature and pressure on the

combination gauge located in the supply piping on
the left side of the boiler. Boiler pressure should
never be higher than 5 psi below the rating shown
on the safety relief valve (25 psig maximum for a 30
psig rating). Boiler temperature should never be
higher than 240° F.

4. Check for water leaks in boiler and system piping.

5. Smell around the appliance area for gas. If you smell

gas, follow the procedure listed in the Lighting
Operating Instructions to shut down appliance in
Section 7, Start-Up Procedure Part B.

B. WEEKLY (WITH BOILER IN USE)

1. Flush float-type low-water cut-off (if used) to remove

sediment from the float bowl as stated in the
manufacturer’s instructions.

C. ANNUALLY (BEFORE START OF

HEATING SEASON)

1. Check boiler room floor drains for proper

functioning.

2. Check function of the safety relief valve by

performing the following test:

a. Check valve piping to determine that it is

properly installed and supported.

b. Check boiler operating temperature and pressure.

c. Lift the try lever on the safety relief valve to the

full open position and hold it for at least five
seconds or until clean water is discharged.

d. Release the try lever and allow the valve to close.

If the valve leaks, operate the lever two or three
times to clear the valve seat of foreign matter. It
may take some time to determine if the valve has
shut completely.

e. If the valve continues to leak, it must be replaced

before the boiler is returned to operation.

f.

Check that operating pressure and temperature
have returned to normal.

g. Check again to confirm that valve has closed

completely and is not leaking.

3. Test low-water cut-off (if used) as described by the

manufacturer.

4. Test limit as described in Section 7, Part C, “Check-

Out Procedure”.

5. Test function of ignition system safety shut-off

features as described in Section 7, Part C, “Check-
Out Procedure”.

6. Remove the top/front jacket panel and inspect for

any foreign debris that may have entered through air
inlet vent.

7. Inspect burner for deterioration. Replace if necessary.

8. With boiler in operation check that condensate is

dripping from drain hose. Check for any restriction in
condensate drain line.

a. CONDENSATE CLEANING INSTRUCTIONS:

1. Turn the thermostat down or off so the

Pinnacle will not cycle and then follow the
steps below.

a. Close manual gas shutoff valve.

b. Disconnect the condensate piping from the

outside connection (not from the Pinnacle)
so flow can be observed.

c. Block the air flow in the exhaust by

temporarily plugging the exhaust from the
outside vent.

9. MAINTENANCE

The following annual inspection must be performed
by a qualified service technician.

CAUTION

When servicing or replacing components, be
absolutely certain that the following conditions are
met:

Water, gas and electricity are off.

The boiler is at room temperature.

There is no pressure in the boiler.

DANGER

MAINTENANCE