D. EXPANSION TANK

1. Consult the tank manufacturer’s instructions for

specific information relating to tank installation. Size
the expansion tank for the required system volume
and capacity. See Table 10.2 in Section 10 for boiler
water capacity.

2. Expansion tanks are available with built-in fill valves

and check valves for reducing supply water pressure
and maintaining minimum system pressure. Check
the design features of the tank and provide valves as
necessary.

Refer back to Figure 3.1 for typical expansion tank piping.

E. INDIRECT-FIRED WATER HEATER

If the boiler is to be used in conjunction with an indirect-
fired water heater, refer to Figure 3.7 for typical piping.
Follow the instructions provided by the water heater
manufacturer. Pipe the water heater as a separate zone.

F.

FREEZE PROTECTION

For new or existing systems that must be freeze-
protected:

1. Glycol in hydronic applications is specially

formulated for this purpose. It includes inhibitors
which prevent the glycol from attacking metallic
system components. Make certain that the system
fluid is checked for the correct glycol concentration
and inhibitor level.

2. The antifreeze solution should be tested at least once

a year and as recommended by the antifreeze
manufacturer.

3. Antifreeze solutions expand more than water. For

example, a 50% by volume solution expands 4.8%
in volume for a temperature increase from 32°F
(0°C) to 180°F (82°C), while water expands 3% with
the same temperature rise. Allowance must be made
for this expansion in system design.

4. For more information, consult the PB Heat LLC

Water Installation Survey and the antifreeze
manufacturer.

Figure 3.7:

Typical Piping with Indirect-Fired Water Heater

WATER PIPING AND CONTROLS

Use only inhibited propylene glycol solutions of up to
50% by volume with water. Ethylene glycol is toxic
and can attack gaskets and seals used in hydronic
systems.

WARNING